| 2001-01-08 00:00:00 | ************UNSAT********************** |
| | |
| | 1)NOTE:AS PER 110-9/215-5 NEED TO SUBMIT |
| | AIC RATING OF EQUIPMENT MAINS, BRKRS. |
| | AIC RATING IS FIGURED FROM FAULT CURRENT |
| | CALCULATIONS. |
| | |
| | 2)NOTE: AS PER 210-52D/215-5 NEED TO |
| | SHOW BATH(S) DEDICATED GFI CIRCUT ON |
| | PANEL SCHEDULE. |
| | |
| | 3)NOTE:AS PER 1993/1996 NFPA-72 |
| | CHAPTER 2-2.1.1.1 SMOKE DETECTORS ARE |
| | REQ`D INSIDE AND OUTSIDE ALL SLEEPING |
| | ROOMS IN NEW DWELLINGS. |
| | |
| | 4)NOTE:RISER DIAGRAM SHOWS ALUM. AS PART |
| | FO THE GROUNDING ELECTRODE,, AS PER |
| | COUNTY AMENDMENT THIS IS NOT ALLOWED. |
| | ONLY COPPER OR GALV. |
| | |
| | 5)NOTE:AS PER NEC TABLES 4/5 PIPE FILL |
| | FOR THE CONDUIT FEEDING POOL PANEL |
| | IS NOT LARGE ENOUGH. PLEASE CORRECT AND |
| | CHANGE CONDUIT SIZE. |
| | |
| | 6)NOTE:AS PER 210-52E NEED TO HAVE REC. |
| | IN FRONT OF DWELLING. |
| | |
| | 7)NOTE: NEC. REQ`S ROOM FOR TWO SPARE |
| | CIRCUTS IN ALL PANELS OF NEW HOMES. |
| | YOUR PLANS SHOW LOAD CALCULATION BEING |
| | 123.8 AMPS AND UTILIZING 125 AMP PANEL. |
| | THIS PANEL IS NOT LARGE ENOUGH AND NEEDS |
| | TO INCREASE TO 150. ALSO THIS DOES NOT |
| | EVEN INCLUDE POOL PANEL OPTION???!!!! |
| | NEED TO SUBMIT LOAD CALCULATION SHOWING |
| | POOL PANEL OPT. TO INCLUDE POOL HEATER, |
| | POOL LIGHT, AND POOL PUMP ETC. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW AND APPROVAL. IF THERE ARE |
| | ANY QUESTIONS PLEASE CALL AT 659-8096 |
| | EXT 8372 |