| Plan Review Notes For Permit 99110631 |
| Permit Number |
99110631 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | THE PERCENTAGE OF WALL OPENINGS EXCEED | | | THE AMOUNT ALLOWED BY TABLE 600. | | | PLAN A3 SIDE ELEVATION, WALL AREA | | | 388SF X 20%= 77.6SF ALLOWED | | | OPENINGS:8X4'6= 36 | | | 4X4'6= 18 | | | 3X4'6= 13.5 | | | DOOR4'6X7= 31.5 | | | 4X4'6= 18 | | | TOTAL117SF | | | 117-77.6= 39.5SF OVER ALLOWED AMOUNT | | | | | | ENCLOSED LANI SIDE: | | | ADD 12X8X20%=19.2SF ADD TO 77.6= 96.8 | | | 117-96.8= 20.2SF OVER ALLOWED AMOUNT | | | | | | PROVIDE SITE SPECIFIC ENGINEERING | | | CALCULATIONS FOR THE EXTERIOR WINDOWS & | | | SLIDING GLASS DOORS WITH EACH PERMIT | | | APPLICATION. | | | | | | SEE COMMENTS FROM PLUMBING AND ELECTRIC | | | REVIEW. | | | | | | PLAN SD1, SD2, SD3, SD4 UPDATE PLAN DATE | | | | | | REMOVE OLD MASTER PERMIT NUMBER FROM | | | PLAN SD2 AND SD4. | | | | | | PROVIDE A TRUSS DESIGN CERTIFICATION | | | FORM FOR THE TRUSS ENGINEERING. ATTACHED | | | IS A COPY OF THE FORM. |
|