| Date |
Text |
| 2001-01-08 00:00:00 | 1-SPECIFY THE DESIGN PRESSURES AT ALL |
| | EXTERIOR OPENINGS.SEC 104.2 CITY AMEND |
| | 2-PRODUCT APPROVALS FOR DOORS AND |
| | WINDOWS TO BE SITE SPECIFIC FOR EACH |
| | HOUSE AND SIGNED, SEALED AND DATE BY |
| | THE MANUFACTURER'S ENGINEER AND BY THE |
| | DESIGNER ENGINEER OF RECORD. |
| | 3-PROVIDE SOIL TEST REPORT AS PER CITY |
| | AMENDMENTS SECTION 1804.2.7. |
| | 4-REVISE SHEET A-2: |
| | -SECTION 2 OF A-2 FOOTING TO HAVE 12" |
| | MIN BELOW GRADE. |
| | -INFILTRATION REQUIREMENTS NOTE IS NOT |
| | CLEAR. SEE FLORIDA ENERGY EFFICIENCY |
| | CODE FOR BUILDING CONSTRUCTION 1997 |
| | EDITION. WHAT'S PRACTICE #2? |
| | 5-ALL 4 SETS OF TRUSS DRAWINGS TO BE |
| | SIGNED, SEALED AND DATED. (EMBOSSED |
| | SEAL AND WET SIGNATURE-NO RUBBER). |
| | 6-GARAGE DOOR: |
| | -SHEET T-1 CALLS FOR A DADE COUNTY |
| | PRODUCT APPROVAL, BUT, PRODUCT |
| | APPROVAL SUBMITTED IS FROM SBCCI. |
| | -SBCCI PRODUCT APPROVAL IS MISSING ONE |
| | PAGE OF THE DRAWINGS. |
| | -PROVIDE PRODUCT APPROVAL OF DOOR |
| | ATTACHED DIRECTLY TO STRUCTURE INSTEAD |
| | OF ATTACHED TO A SUB-BUCK. |
| | 7-PRODUCT APPROVAL FOR ENTRY DOOR IS FOR |
| | AN OUTSWING DOOR AND FLOOR PLANS CALL |
| | FOR AN INSWING DOOR. RESUBMIT PRODUCT |
| | APPROVAL. |