| Plan Review Notes For Permit 99110630 |
| Permit Number |
99110630 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************UNSAT******************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT MAINS AND BRKRS. AIC RATING IS | | | FIGURED FROM FAULT CURRENT CALCULATIONS. | | | | | | 2)NOTE: NEED TO INCLUDE AS PART OF THE | | | GROUNDING ELECTRODE SYSTEM; GRND.ROD, | | | BLDG.STEEL AND COLD WATER PIPE. AS PER | | | 250-81. | | | | | | 3)NOTE: AS REQ`D BY 210-52D/215-5 NEED | | | TO INCLUDE ON PANEL SCHEDULE BATH(S) | | | DEDICATED 20AMP GFI CIRCUT(S). | | | | | | 4)NOTE: AS PER NEC AND 1993/1996 NFPA-72 | | | 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS | | | IN NEW DWELLINGS. | | | | | | NEED TO SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL. IF THERE ANY | | | QUESTIONS CALL 659-8096 EXT.8372 |
|