| Plan Review Notes For Permit 99110592 |
| Permit Number |
99110592 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************PROVISO***************** | | | | | | 1)NOTE:NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT MAINS AND BRANCH BRKRS. AS | | | PER ARTS;110-9/215-5 | | | 2)NOTE:KITCHEN WALL MISSING OUTLET REQ`D | | | AS PER 210-52 | | | 3)NOTE:AS PER 210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | 4)NOTE:PLEASE SHOW ON PANEL SCHEDULE | | | CIRCUT REQ`D FOR BATH(S) REQ`D AS PER | | | ART;210-52D | | | 5)NOTE: SMOKE DETECTORS ARE REQ`D | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS | | | IN NEW DWELLINGS. AS PER 1993-96 NFPA-72 | | | 2-2.1.1.1 | | | 6)NOTE:EQUIPMENT GROUND REQ`D AFTER | | | FIRST MEANS OF DISC. AND SIZED PER | | | 250-95 | | | | | | NEED TO SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL BEFORE FIRST | | | ROUGH ELECTRICAL INSPECTION IS CALLED IN |
|