Plan Review Notes
Plan Review Notes For Permit 99110592
Permit Number 99110592
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************PROVISO*****************
  
 1)NOTE:NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS AND BRANCH BRKRS. AS
 PER ARTS;110-9/215-5
 2)NOTE:KITCHEN WALL MISSING OUTLET REQ`D
 AS PER 210-52
 3)NOTE:AS PER 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 4)NOTE:PLEASE SHOW ON PANEL SCHEDULE
 CIRCUT REQ`D FOR BATH(S) REQ`D AS PER
 ART;210-52D
 5)NOTE: SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 IN NEW DWELLINGS. AS PER 1993-96 NFPA-72
 2-2.1.1.1
 6)NOTE:EQUIPMENT GROUND REQ`D AFTER
 FIRST MEANS OF DISC. AND SIZED PER
 250-95
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION IS CALLED IN