2001-01-08 00:00:00***************PROVISO******************
  
 1)NOTE: AS PER 110-9/215-5 NEED TO
 AIC RATING OF EQUIPMENT MAINS/BRKRS.
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
  
 2)NOTE:AS PER ART;210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
  
 3)NOTE:PLEASE DRAW IN DISC. REQ`D FOR
 A/C COND. UNIT AS PER 440-11.
  
 4)NOTE:RISER DIAGRAM SHOWS MAIN DISC.
 PLANS ONLY SHOW METER?? PLEASE CORRECT.
  
 5)NOTE:AS PER 1993/1996 NFPA-72
 CHAPTER 2-2.1.1.1 SMOKE DETECTORS ARE
 REQ`D INSIDE AND OUTSIDE ALL SLEEPING
 ROOMS IN NEW DWELLINGS.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE ROUGH
 ELECTRICAL INSPECTION.