| 2001-01-08 00:00:00 | ***************PROVISO****************** | | | | | | 1)NOTE: AS PER 110-9/215-5 NEED TO | | | AIC RATING OF EQUIPMENT MAINS/BRKRS. | | | AIC RATING IS FIGURED FROM FAULT CURRENT | | | CALCULATIONS. | | | | | | 2)NOTE:AS PER ART;210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | | | | 3)NOTE:PLEASE DRAW IN DISC. REQ`D FOR | | | A/C COND. UNIT AS PER 440-11. | | | | | | 4)NOTE:RISER DIAGRAM SHOWS MAIN DISC. | | | PLANS ONLY SHOW METER?? PLEASE CORRECT. | | | | | | 5)NOTE:AS PER 1993/1996 NFPA-72 | | | CHAPTER 2-2.1.1.1 SMOKE DETECTORS ARE | | | REQ`D INSIDE AND OUTSIDE ALL SLEEPING | | | ROOMS IN NEW DWELLINGS. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL BEFORE ROUGH | | | ELECTRICAL INSPECTION. |
|