2001-01-08 00:00:001- PROVIDE A LOAD CALCULATION FOR TRANS.
 #T1215-5
  
 2-THE LOAD SIDE OF TRANS. #T3 HAS TO BE
 WITHIN 25' OF PANEL F240-21
  
 3-NEED FAULT CURRENT FOR MDP110-9
  
 4-SERVICES ARE TO HAVE PLAQUES STATING
 SERVICE ONE OF TWO WITH THE LOCATION
 OF THE OTHER SERVICE AND TWO OF TWO
 WITH THE LOCATION OF THE OTHER SERVICE
 PER 230-2B!!!!!!!!!!!!!!!!!!!!!!!!!
  
 5-SUBMIT THE REQUESTED PRIOR TO FINAL
 SO PLANS WILL BE ON JOB FOR THE FINAL