| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1- PROVIDE A LOAD CALCULATION FOR TRANS. | | | #T1215-5 | | | | | | 2-THE LOAD SIDE OF TRANS. #T3 HAS TO BE | | | WITHIN 25' OF PANEL F240-21 | | | | | | 3-NEED FAULT CURRENT FOR MDP110-9 | | | | | | 4-SERVICES ARE TO HAVE PLAQUES STATING | | | SERVICE ONE OF TWO WITH THE LOCATION | | | OF THE OTHER SERVICE AND TWO OF TWO | | | WITH THE LOCATION OF THE OTHER SERVICE | | | PER 230-2B!!!!!!!!!!!!!!!!!!!!!!!!! | | | | | | 5-SUBMIT THE REQUESTED PRIOR TO FINAL | | | SO PLANS WILL BE ON JOB FOR THE FINAL |
|