| Date |
Text |
| 2001-01-08 00:00:00 | STAFF LOUNGE SINK SHALL COMPLY FULLY W/ |
| | FACBC SEC.4.24.1.- 4.24.7. |
| | |
| | WOMEN'S TOILET STALL SHALL COMPLY W/ |
| | FACBC SEC.4.17.3(SEE EXCEPTION:NEW |
| | CONSTRUCTION) |
| | |
| | DOOR ON TOILET STALL IN WOMEN'S R.R. |
| | DOESN'T PERMIT USE OF WATER CLOSET. |
| | COMPLY W/SPC SEC.404. |
| | |
| | DRINKING FOUNTAIN SHALL COMPLY W/FACBC |
| | SEC.4.1.3.(10)(A).PROVISIONS SHALL BE |
| | MADE FOR PEOPLE WHO HAVE TROUBLE |
| | BENDING OR STOOPING. |
| | |
| | SIZE OF VENTING FOR PLBG.FIXTURES SHALL |
| | COMPLY W/SPC TABLE 920.2. |
| | |
| | NOT MORE THAN 2 WATER CLOSETS PERMITTED |
| | ON 3" BUILDING DRAIN PER TABLE 714.1, |
| | FOOTNOTE #3. |
| | |
| | RELIEF VALVE DRAIN SHALL DISCHARGE TO A |
| | FLOOR SINK/WASTE RECEPTOR TO PREVENT |
| | SPLASHING.SPC SEC.507.8.4. |
| | |
| | SUBMIT OCCUPANT LOAD AND SQ.FOOTAGE OF |
| | SPACE TO ENSURE COMPLIANCE W/SPC TABLE |
| | 407. |
| | |
| | WALLS AND FLOORS IN TOILET ROOMS SHALL |
| | COMPLY W/SBC SEC.1204.2. |
| | |
| | *****NOTE:THESE ARE THE EXACT SAME |
| | COMMENTS EXCEPT ONE FROM PLAN REVIEW |
| | DATED 11/24/99 AND NOT ONE ITEM HAS BEEN |
| | CORRECTED.DO NOT RESUBMIT THESE PLANS |
| | FOR PLUMBING REVIEW UNTIL ALL ITEMS |
| | HAVE BEEN CORRECTED ACCORDING TO THE |
| | STANDARD PLBG.AND BUILDING CODE. |