Plan Review Notes
Plan Review Notes For Permit 99110434
Permit Number 99110434
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00STAFF LOUNGE SINK SHALL COMPLY FULLY W/
 FACBC SEC.4.24.1.- 4.24.7.
  
 WOMEN'S TOILET STALL SHALL COMPLY W/
 FACBC SEC.4.17.3(SEE EXCEPTION:NEW
 CONSTRUCTION)
  
 DOOR ON TOILET STALL IN WOMEN'S R.R.
 DOESN'T PERMIT USE OF WATER CLOSET.
 COMPLY W/SPC SEC.404.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 SIZE OF VENTING FOR PLBG.FIXTURES SHALL
 COMPLY W/SPC TABLE 920.2.
  
 NOT MORE THAN 2 WATER CLOSETS PERMITTED
 ON 3" BUILDING DRAIN PER TABLE 714.1,
 FOOTNOTE #3.
  
 RELIEF VALVE DRAIN SHALL DISCHARGE TO A
 FLOOR SINK/WASTE RECEPTOR TO PREVENT
 SPLASHING.SPC SEC.507.8.4.
  
 SUBMIT OCCUPANT LOAD AND SQ.FOOTAGE OF
 SPACE TO ENSURE COMPLIANCE W/SPC TABLE
 407.
  
 WALLS AND FLOORS IN TOILET ROOMS SHALL
 COMPLY W/SBC SEC.1204.2.
  
 *****NOTE:THESE ARE THE EXACT SAME
 COMMENTS EXCEPT ONE FROM PLAN REVIEW
 DATED 11/24/99 AND NOT ONE ITEM HAS BEEN
 CORRECTED.DO NOT RESUBMIT THESE PLANS
 FOR PLUMBING REVIEW UNTIL ALL ITEMS
 HAVE BEEN CORRECTED ACCORDING TO THE
 STANDARD PLBG.AND BUILDING CODE.