| Plan Review Notes For Permit 99110434 |
| Permit Number |
99110434 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | STAFF LOUNGE SINK SHALL BE ACCESSIBLE | | | PER FACBC SEC.4.24.1- 4.24.7. | | | | | | WOMENS TOILET STALL SHALL COMPLY W/FACBC | | | SEC.4.17.3 | | | (SEE EXCEPTION:NEW CONSTRUCTION.) | | | | | | DOOR ON TOILET STALL IN WOMEN'S R.R.DOES | | | NOT PERMIT USE OF FIXTURE.COMPLY W/SPC | | | SEC.404. | | | | | | DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | | SEC.4.1.3.(10)(A).PROVISIONS SHALL BE | | | MADE FOR PEOPLE WHO HAVE TROUBLE BENDING | | | OR STOOPING. | | | | | | SIZE OF VENTING FOR PLBG.FIXTURES SHALL | | | COMPLY W/SPC TABLE 920.2. | | | | | | MORE THAN 2 W.C.'S NOT PERMITTED ON 3" | | | BUILDING DRAIN.SPC TABLE 714.1,FOOTNOTE | | | #3. | | | | | | RELIEF VALVE DRAIN SHALL DISCHARGE TO A | | | FLOOR SINK/WASTE RECEPTOR TO PREVENT | | | SPLASHING.SPC 507.8.4. | | | | | | SUBMIT OCCUPANT LOAD AND SQ.FOOTAGE OF | | | SPACE TO ENSURE COMPLIANCE W.SPC SEC. | | | TABLE |
|