Plan Review Notes
Plan Review Notes For Permit 99110434
Permit Number 99110434
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00STAFF LOUNGE SINK SHALL BE ACCESSIBLE
 PER FACBC SEC.4.24.1- 4.24.7.
  
 WOMENS TOILET STALL SHALL COMPLY W/FACBC
 SEC.4.17.3
 (SEE EXCEPTION:NEW CONSTRUCTION.)
  
 DOOR ON TOILET STALL IN WOMEN'S R.R.DOES
 NOT PERMIT USE OF FIXTURE.COMPLY W/SPC
 SEC.404.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 SIZE OF VENTING FOR PLBG.FIXTURES SHALL
 COMPLY W/SPC TABLE 920.2.
  
 MORE THAN 2 W.C.'S NOT PERMITTED ON 3"
 BUILDING DRAIN.SPC TABLE 714.1,FOOTNOTE
 #3.
  
 RELIEF VALVE DRAIN SHALL DISCHARGE TO A
 FLOOR SINK/WASTE RECEPTOR TO PREVENT
 SPLASHING.SPC 507.8.4.
  
 SUBMIT OCCUPANT LOAD AND SQ.FOOTAGE OF
 SPACE TO ENSURE COMPLIANCE W.SPC SEC.
 TABLE