| Plan Review Notes For Permit 99110356 |
| Permit Number |
99110356 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************PROVISO***************** | | | | | | 1)NOTE:NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT MAINS AND BRKRS. AIC RATING IS | | | FIGURED FROM FAULT CURRENT CALCULATIONS. | | | AS PER ART; 110-9/215-5 | | | | | | 2)NOTE:AS PER 1993/1996 NFPA-72 2-2.1.1 | | | .1 SMOKE DETECTORS ARE REQ`D INSIDE AND | | | OUTSIDE ALL SLEEPING ROOMS OF NEW | | | DWELLINGS. | | | | | | 3)NOTE:AS PER 210-52D PLEASE INCLUDE | | | BATH(S) GFI CIRCUT ON PANEL SCHEDULE. | | | 20 AMP,#12 AWG. DEDICATED. | | | | | | 4)NOTE:AS PER 210-8-A-6 ALL RECEPTS. | | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | | | | 5)NOTE: PLANS SHOW MAIN DISCONNECT NEXT | | | TO METERCAN,,,,,POWER RISER SHOWS NO | | | MAIN?? WHICH IS IT? ALSO IF 200 AMP | | | SERVICE IS GOING TO BE AN OPTION THEN | | | DRAW SECOND RISER WITH WIRE SIZES, | | | CONDUIT SIZE, AND APPRO. GROUND. | | | | | | 6)NOTE: AS PER 250-81/215-5 PLEASE INCL. | | | COLD WATER PIPE AS PART OF THE GROUNDING | | | SYSTEM. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND APPROVAL BEFORE FIRST ROUGH | | | ELECTRICAL INSPECTION IS CALLED IN. THIS | | | WOULD INCLUDE GROUND ROUGH IF ANY. |
|