| Plan Review Notes For Permit 99110353 |
| Permit Number |
99110353 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************PROVISO******************* | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT AND MAINS. TO INCLUDE BRKRS. | | | AIC RATING IS FIGURED FROM FAULT CURRENT | | | CALCULATIONS. REQUESTED AS PER 110-9/ | | | 215-5 | | | | | | 2)NOTE: AS PER 1993/1996 NFPA-72 | | | 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS IN | | | NEW DWELLINGS. | | | | | | 3)NOTE:AS REQ`D PER ARTS:210-52D/215-5 | | | PLEASE INCLUDE DEDICATED BATH GFI CIRCUT | | | (S) ON PNAEL SCHEDULE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND APPROVAL BEFORE FIRST ROUGH | | | ELECTRICALINSPECTION IS CALLED IN. |
|