| Plan Review Notes For Permit 99110346 |
| Permit Number |
99110346 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO | | | REQUIREMENTS OF CHAPTER 11 1997 SMC | | | LEVEL 1 MACHINERY ROOM TO BE COMPLIED W/ | | | 1)OPENINGS INTO ADJACENT ROOMS ARE PROHI | | | BITED (SEAL 100%) | | | 2) REFRIGERANT LEAK DETECTOR REQUIRED | | | 3) NO OPEN FLAMES USING COMBUSTION AIR | | | PERMITTED WITHIN THE ROOM | | | 4) SIGNS SHALL BE POSTED PROHIBITING | | | UNAUTHORIZED ACCESS AND EXPLAINING PROCE | | | DURE | | | 5) VENTILATION PER 1105.7.5 TO BE PROVID | | | ED SUPPLY CALCULATIONS | | | 6) RELIEF DEVICES TO BE INSTALLED PER | | | SMC 1105.9 | | | 7) BREATHING APPARATUS NOT REQUIRED PRO | | | VIDED SIGNAGE IS INCLUSIVE OF PROCEEDURE | | | IF LEAK OCCURS | | | 8) REFER TO 1997 SMC FOR CLARIFICATION | | | OF ABOVE ISSUES | | | 9) PROVIDE PRESSURE TEST PRIOR TO INSULA | | | TING PIPING |
|