| Plan Review Notes For Permit 99110337 |
| Permit Number |
99110337 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SHT.ME-2-GENEREAL REFERENCES TO CODE ARE | | | NOT PERMITTED PER COUNTYWIDE AMENDMENTS | | | TOP SPC SEC.104.2.1. | | | | | | A DRINKING FOUNTAIN IS REQD.PER SPC | | | TABLE 407.THERE IS NO EXCEPTION. | | | | | | SIZE OF HANDICAP STALLS SHALL COMPLY W/ | | | FACBC SEC.4.1.6(B),4.17.3. | | | | | | LOCATION OF PLBG.FIXTURES ON SANITARY | | | RISER SHALL MATCH FLOOR PLAN.(SEE LAV.IN | | | WOMEN'S RESTROOM.CITY OF WPB AMENDMENTS | | | TO SPC SEC.104.2.1. | | | | | | BREAKROOM SINK SHALL COMPLY W/FACBC | | | SECS.4.24.1.-4.24.7.(MAX.HT.TO BE 34") |
|