| Plan Review Notes For Permit 99110337 |
| Permit Number |
99110337 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | BREAKROOM SINK SHALL COMPLY W/FACBC SEC. | | | 4.24.1- 4.24.7. | | | | | | A DRINKING FOUNTAIN IS REQD.PER TABLE | | | 407 AND SHALL BE HANDICAP ACCESSIBLE PER | | | FACBC 4.1.3(10)(A),4.15. | | | | | | WIDTH OF HANDICAP STALLS SHALL COMPLY W/ | | | FACBC SEC.4.17.3(SEE EXCEPTION:NEW | | | CONSTRUCTION.) | | | | | | URINAL SHALL BE HANDICAP ACCESSIBLE AND | | | COMPLY W/FACBC SEC.4.18.1- 4.18.4. | | | | | | FLOOR DRAINS SHALL BE EQUIPPED W/TRAP | | | PRIMERS.SPC SEC.409.4.1.1. | | | | | | LAV.IN WOMEN'S R.R.MISSING FROM SANITARY | | | RISER. | | | | | | VENT FOR URINAL CANNOT INCREASE IN SIZE. | | | SPC 905.2.,904.3.1. | | | | | | OVER 2 FIXTURES SUPPLIED BY 1/2"COLD | | | WATER.MODELWIDE AMENDMENTS TO STD.PLBG | | | CODE SEC.607.7 |
|