Plan Review Notes
Plan Review Notes For Permit 99110337
Permit Number 99110337
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00BREAKROOM SINK SHALL COMPLY W/FACBC SEC.
 4.24.1- 4.24.7.
  
 A DRINKING FOUNTAIN IS REQD.PER TABLE
 407 AND SHALL BE HANDICAP ACCESSIBLE PER
 FACBC 4.1.3(10)(A),4.15.
  
 WIDTH OF HANDICAP STALLS SHALL COMPLY W/
 FACBC SEC.4.17.3(SEE EXCEPTION:NEW
 CONSTRUCTION.)
  
 URINAL SHALL BE HANDICAP ACCESSIBLE AND
 COMPLY W/FACBC SEC.4.18.1- 4.18.4.
  
 FLOOR DRAINS SHALL BE EQUIPPED W/TRAP
 PRIMERS.SPC SEC.409.4.1.1.
  
 LAV.IN WOMEN'S R.R.MISSING FROM SANITARY
 RISER.
  
 VENT FOR URINAL CANNOT INCREASE IN SIZE.
 SPC 905.2.,904.3.1.
  
 OVER 2 FIXTURES SUPPLIED BY 1/2"COLD
 WATER.MODELWIDE AMENDMENTS TO STD.PLBG
 CODE SEC.607.7