Plan Review Notes
Plan Review Notes For Permit 99110337
Permit Number 99110337
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PROVISO:
 DUCT SMOKE DETECTOR TO BE TIED TO BLDG
 FIRE ALARM OR IF NO BLDG FIRE ALARM SYST
 EM, TIED TO HORN AND STROBE FOR NOTIFI-
 CATION PER NFPA 4-4.4.2 OR 4-4.4.3
 AREAS WITH 300 CFM OR MORE TO HAVE R/A
 FROM AREA