Plan Review Notes
Plan Review Notes For Permit 99110196
Permit Number 99110196
Review Stop P
Sequence Number 6
Notes
Date Text
2001-05-29 00:00:00PLUMBING PLAN REVIEW 6TH TIME DENIED
 THIS PERMIT WILL NOT BE ISSUED UNTIL ALL
 COMMENTS ARE ADDRESSED.
 (1) SHT A-5 PROVIDE INFORMATION ON
 ROOF DRAINAGE,GUTTER AND DOWN SPOUTS,
 SIZE AND NUMBER.SPC 94 SEC 1101.2
 (2)DWV ISOMETRIC FOR EA PLUMBING
 FIXTURE, WITH PIPE SIZES SPC94 SEC 104.3
 (3) SHT A-6,A-10 H/C REST RM'S COMPLY
 WITH FACBC 97 SEC 4.16& FIG 28.
 SHOW SCALE OF DETAIL,CLEAR FLR SPACE.
 (4) SHT A-6 COMPLY W/FACBC 97 SEC 4.15.5
 & FIG 27,FOR A H/C DRINKING FOUNTAIN.
 (5) SHT P-1.0 SHOW LOCATION & TYPE OF
 BACK FLOW PREVENTER. SPC-97 SEC 606.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 561-659-8096X 8233