| Plan Review Notes For Permit 99110196 |
| Permit Number |
99110196 |
|
| Review Stop |
P |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2001-05-29 00:00:00 | PLUMBING PLAN REVIEW 6TH TIME DENIED | | | THIS PERMIT WILL NOT BE ISSUED UNTIL ALL | | | COMMENTS ARE ADDRESSED. | | | (1) SHT A-5 PROVIDE INFORMATION ON | | | ROOF DRAINAGE,GUTTER AND DOWN SPOUTS, | | | SIZE AND NUMBER.SPC 94 SEC 1101.2 | | | (2)DWV ISOMETRIC FOR EA PLUMBING | | | FIXTURE, WITH PIPE SIZES SPC94 SEC 104.3 | | | (3) SHT A-6,A-10 H/C REST RM'S COMPLY | | | WITH FACBC 97 SEC 4.16& FIG 28. | | | SHOW SCALE OF DETAIL,CLEAR FLR SPACE. | | | (4) SHT A-6 COMPLY W/FACBC 97 SEC 4.15.5 | | | & FIG 27,FOR A H/C DRINKING FOUNTAIN. | | | (5) SHT P-1.0 SHOW LOCATION & TYPE OF | | | BACK FLOW PREVENTER. SPC-97 SEC 606. | | | END OF COMMENTS PAUL SCHMITZ | | | QUESTIONS 561-659-8096X 8233 |
|