| 2001-05-07 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 99110196 |
| | 6107 S DIXIE HWY |
| | |
| | 1)- DISCREPANCY SHEET A-2 NOTES THAT ALL |
| | SECOND STORY STAIRWELL DOORS HAVE A 1 HR |
| | RATING, THIS DOOR IS (2) BUT THE SAME |
| | DOOR (2) IS INDICATED FOR THE RESTROOMS |
| | ON THE FIRST FLOOR. |
| | |
| | 2)- STORAGE & MERCANTILE TO HAVE (1 HR) |
| | SEPERATION SHOW U.L. RATING FOR THE |
| | CEILING FLOOR ASSEMBLY. |
| | |
| | 3)- SHEET A-2 DEPICTS THE OCCUPANCY TO |
| | BE STORAGE, SBC TABLE 1604.1 STORAGE |
| | LIGHT THE FLOOR LOADING IS TO BE 125 LBS |
| | LIVE LOAD. |
| | |
| | 4)- ADMINISTRATIVE CODE 106.4 .2. |
| | STORAGE & FACTORY OCCUPANCIES. IT SHALL |
| | BE THE RESPONSIBILITY OF THE OWNER, |
| | AGENT, PROPRIETOR OR OCCUPANT OF GROUP S |
| | OR GROUP F OCCUPANCIES, TO EMPLOY A COMP |
| | ETENT ARCHITECT OR ENGINEER IN COMPUTING |
| | SAFE LOAD CAPACITY.ALL SUCH COMPUTATIONS |
| | SHALL BE ACCOMPANIED BY AN AFFIDAVIT |
| | FROM THE ARCHITECT OR ENGINEER STATING |
| | THE SAFE FLOOR LOADS ON EACH FLOOR IN |
| | POUNDS PER SQUARE FOOT UNIFORMLY DISTRIB |
| | UTED. THE COMPUTATIONS AND AFFIDAVITE |
| | SHALL BE FILED AS A PERMANENT RECORD OF |
| | THE BUILDING DEPARTMENT. |
| | |
| | 5)- ADMINISTRATIVE CODE 106.4.3 |
| | SIGNS REQUIRED FOR EVERY PART OF THE |
| | BUILDING THAT WILL BE USED FOR STORAGE. |
| | THE SIGNS SHALL STATE TTTHE SAFE FLOOR |
| | LOADS AS REVIEWED BY THE BUILDING DEPART |
| | MENT WHICH BE SUPPLIED & SECURELY |
| | AFFIXED BY THE OWNER OF THE BUILDING IN |
| | A CONSPICUOUS PLACE IN EVERY STORY TO |
| | WHICH THEY RELATE. |
| | |
| | 6)- SBC 1606.2.6.2 COMPONENTS & CLADDING |
| | THE INFORMATION SUBMITTED ON THE FRONT |
| | DOORS SI FOR SMALL MISSLE IMPACT ONLY, |
| | THE CITY REQUIRES TESTING FOR LARGE |
| | MISSLE IMPACT TESTING,2 COPIES FOR EACH |
| | PRODUCT. DADE COUNTY OR S.B.C.C.I. |
| | REPORT ARE ACCEPTED. THIS CAN BE A |
| | "PROVISO" TO BE SUBMITTED BEFORE THE |
| | FIRST INSPECTION. |
| | |
| | 7)- THE ROOFING CUT SHEET WILL BE ACCEPT |
| | ABLE TO SHOW IT COMPLIES TO THE REQUIRE- |
| | MENTS OF THE FIRE DISTRICT. WE ALSO NEED |
| | PRODUCT TESTING FOR 110 MPH WIND ZONES |
| | SBC 1503..3.2/1503.4.1.2.DADE COUNTY OR |
| | SBCCI REPORT ARE ACCEPTABLE,THIS COULD |
| | ALSO BE A "PROVISO" TO BE SUBMITTED AS A |
| | SEPERATE PERMIT. |
| | |
| | 8)- SUBMIT PLANS TO COUNTY FOR IMPACT |
| | FEES, IF THERE WAS A STRUCTURE THERE |
| | BEFORE THERE MAY BE A CREDIT DUE FOR THE |
| | DEMO. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | 659-8096 EX 8412 |