| 2001-02-27 00:00:00 | ****************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE SHEET E1.0, PLANS |
| | SHOW SEPARATE SERVICES BETWEEN THE TWO |
| | CENTER BAYS , PLEASE SHOW CLARIFICATION |
| | ON TENANT SEPARATION. PLANS DON'T |
| | SHOW THE REQ`D TWO(2) HR FIRE WALL UP TO |
| | ROOF DECK. 230-2.230-72 |
| | |
| | 2)NOTE: PLEASE SEE E-1.0 PLANS HAVE BOTH |
| | 1ST AND 2ND FLOOR LABELED 2ND FLOOR?? |
| | PLEASE CORRECT. |
| | |
| | 3)NOTE: PLEASE PROVIDE CLARIFICATION |
| | FOR MAINS, PANELS ARE SHOWN AS HAVING |
| | MCB AND YET THERE ARE MAIN DISCONNECTS |
| | ON OUTSIDE OF BLDG.??WHICH ONE OR IS IT |
| | BOTH? |
| | |
| | 4)NOTE: PLEASE PROVIDE CLARIFICATION |
| | FOR MEANS OF EGRESS LIGHTING FOR STAIR |
| | TRAVEL UP AND DOWN? 3-WAY SWITCHES???? |
| | |
| | 5)NOTE: PLEASE NOTE PER LOCAL AND COUNTY |
| | WIDE CODE, OUTLET SPACING IS TO MEET |
| | 20` OF WALL,INSTORAGE SPACE 210-50 |
| | |
| | 6)NOTE:PLEASE SHOW BRANCH CIRCUIT #`S |
| | ON PLANS THAT CORRELATE TO SUBMITTED |
| | PANEL SCHEDULES. |
| | |
| | 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 8)NOTE: PLEASE NOTE EQUIPMENT GROUNDING |
| | CONDUCTOR REQ`D AFTER FIRST MEANS OF |
| | DISCONNECT. 250-122 |
| | |
| | 9)NOTE PLEASE SHOW ALL SERVICE CONDUCTOR |
| | -S RISER/METER ECT. 215-5 |
| | |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |