2001-02-27 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE SEE SHEET E1.0, PLANS
 SHOW SEPARATE SERVICES BETWEEN THE TWO
 CENTER BAYS , PLEASE SHOW CLARIFICATION
 ON TENANT SEPARATION. PLANS DON'T
 SHOW THE REQ`D TWO(2) HR FIRE WALL UP TO
 ROOF DECK. 230-2.230-72
  
 2)NOTE: PLEASE SEE E-1.0 PLANS HAVE BOTH
 1ST AND 2ND FLOOR LABELED 2ND FLOOR??
 PLEASE CORRECT.
  
 3)NOTE: PLEASE PROVIDE CLARIFICATION
 FOR MAINS, PANELS ARE SHOWN AS HAVING
 MCB AND YET THERE ARE MAIN DISCONNECTS
 ON OUTSIDE OF BLDG.??WHICH ONE OR IS IT
 BOTH?
  
 4)NOTE: PLEASE PROVIDE CLARIFICATION
 FOR MEANS OF EGRESS LIGHTING FOR STAIR
 TRAVEL UP AND DOWN? 3-WAY SWITCHES????
  
 5)NOTE: PLEASE NOTE PER LOCAL AND COUNTY
 WIDE CODE, OUTLET SPACING IS TO MEET
 20` OF WALL,INSTORAGE SPACE 210-50
  
 6)NOTE:PLEASE SHOW BRANCH CIRCUIT #`S
 ON PLANS THAT CORRELATE TO SUBMITTED
 PANEL SCHEDULES.
  
 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 8)NOTE: PLEASE NOTE EQUIPMENT GROUNDING
 CONDUCTOR REQ`D AFTER FIRST MEANS OF
 DISCONNECT. 250-122
  
 9)NOTE PLEASE SHOW ALL SERVICE CONDUCTOR
 -S RISER/METER ECT. 215-5
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372