| Plan Review Notes For Permit 99110196 |
| Permit Number |
99110196 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: NOTES STILL NOT ADDRESSED??????? | | | | | | CALLED AND LEFT MESSAGE FOR RETURN CALL | | | FOR EXPLANATION. | | | | | | 2)NOTE: SUBMIT LOAD CALCULATIONS UNDER | | | ART;220 OF THE NEC. | | | SHOW ALL CONTINUOUS LOADS AT 125% ETC. | | | STILL MISSING ELECTRICAL REQ`D FOR | | | SECOND FLOOR MISSING FROM E-DRAWINGS. | | | | | | | | | PLEASE SUBMIT ALL THE INFORMATION ASKED | | | FOR FROM PREVIOUS NOTES AND THESE NOTES. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|