| Plan Review Notes For Permit 99110196 |
| Permit Number |
99110196 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | BUILDING REVIEW COMMENTS | | | -------------------------- | | | DEAR MR.FAGAN, | | | RESPONSE TO YOUR LETTER OF JULY 12,2000, | | | ITEMS NOTED 1 THRU 11, | | | | | | 1]1987 SURVEY PROVIDED IS NOT CONSIDERED | | | CURRENT,PLEASE PROVIDE SIGNED AND | | | SEALED COPY DATED WITHIN 2 YEARS. | | | 2]COMPLIANCE WITH TABLE 600[SBC] HAS NOT | | | BEEN ACHIEVED. | | | 3]SOIL INVESTIGATION REPORT WAS NOT | | | PROVIDED. | | | 4] OK | | | 5]TRAVEL DISTANCE IS MEASURED THE MOST | | | REMOTE POINT TO THE EXIT,INCLUDING THE | | | 2ND FLOOR STORAGE. | | | 6]STRUCTURAL DESIGN ENGINEER SHALL | | | SUBMIT CALCULATIONS FOR ALL LOAD | | | BEARING CONDITIONS. | | | 7]STAIR DETAIL IS NOT COMPLETE,SUBMIT | | | GUARDRAIL AND HANDRAIL DETAILS COMPLY | | | WITH 1007[SBC]. | | | 8]DETAIL PARAPET SUPPORTS. | | | 9]SUBMIT PRODUCT TESTING FOR DOORS AND | | | WINDOWS,ROOF COVERING AND STORM | | | SHUTTERS. | | | 10]IMPACT AND RADON FEES DUE. | | | | | | | | | REVIEWED BY; | | | LUIS MARTINEZ | | | 659-8096#8456 |
|