Plan Review Notes
Plan Review Notes For Permit 99110196
Permit Number 99110196
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 2ND TIME DENIED
 (1) SUBMIT DWV AND WATER LINE DIAGRAMS,
 SHOW LOCATION OF BACK FLOW PREVENTER,
 WATER HEATERS,AND SEPERATE WATER SUPPLY
 TO EACH UNIT WITH SHUT OFF VALVE.
 SPC 94 SEC 101.4.6
 (2) COMPLY WITH FACBC SEC 4.2.3,4.16,
 4.19.3.CLEAR FLOOR SPACE FOR WHEELCHAIR
 IN FRONT OF WATER CLOSET,LAV.
 (3) DRINKING FOUNTAIN REQUIRED FOR EACH
 UNIT SPC 94 TAB 407.
 COMPLY WITH FACBC 4.1.3 (10)(A),4.15.
 END OF COMMENTS