2001-03-06 00:00:001) EXISTING FIRE HYDRANTS NOT SHOWN ON
 SITE PLAN.
 2) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.
 3) IN CLASS C MERCANTILE OCCUPANCIES,
 A MINIMUM OF TWO EXITS ARE REQUIRED.
 ADDITIONAL EXIT SIGNS ARE REQUIRED ABOVE
 REAR EXIT DOORS.
 4) IF SECOND FLOOR IS USED FOR STORAGE,
 IT MUST BE SEPARATED BY AT LEAST ONE
 HOUR FROM THE FIRST FLOOR AND ALL
 OPENINGS MUST BE PROTECTED WITH RATED
 FIRE DOORS EQUIPPED WITH SELF-CLOSING
 DEVICES.
 5) NO INTERIOR FINISH INFORMATION
 PROVIDED WITH PLANS.
 6) TENANT SEPARATIONS TO COMPLY WITH
 BUILDING CODE REQUIREMENTS.
  