| Notes |
| Date |
Text |
| 2001-03-06 00:00:00 | 1) EXISTING FIRE HYDRANTS NOT SHOWN ON | | | SITE PLAN. | | | 2) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. BUILDING ADDRESS TO | | | COMPLY WITH CITY CODE REQUIREMENTS. | | | 3) IN CLASS C MERCANTILE OCCUPANCIES, | | | A MINIMUM OF TWO EXITS ARE REQUIRED. | | | ADDITIONAL EXIT SIGNS ARE REQUIRED ABOVE | | | REAR EXIT DOORS. | | | 4) IF SECOND FLOOR IS USED FOR STORAGE, | | | IT MUST BE SEPARATED BY AT LEAST ONE | | | HOUR FROM THE FIRST FLOOR AND ALL | | | OPENINGS MUST BE PROTECTED WITH RATED | | | FIRE DOORS EQUIPPED WITH SELF-CLOSING | | | DEVICES. | | | 5) NO INTERIOR FINISH INFORMATION | | | PROVIDED WITH PLANS. | | | 6) TENANT SEPARATIONS TO COMPLY WITH | | | BUILDING CODE REQUIREMENTS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|