2001-01-08 00:00:00BUILDING-STRUCTURAL
 ---------------------
  
 1]PROVIDE A CURRENT SIGNED AND SEALED
 SURVEY.
 2]SUBMIT DETERMINATION OF CONSTRUCTION
 TYPE,SEE TABLE 600[97SBC]FOR EXTERIOR
 WALL REQUIREMENTS,ALSO APPENDEX"F".
 3]PROVIDE SOIL INVESTIGATION INFORMATION
 [SITE WAS PREVIOUSLY SERVICE STATION].
 4]PROVIDE ACCESSIBILITY TO 2ND LEVEL,
 MAIN ENTRENCE DOORS ARE NOT ACCESSIBLE
 DOOR REQUIRES A MINIMUM OF 18 INCHES
 CLEARENCE AT THE PULL SIDE OF HANDLE.
 2'8"DOORS AT RESTROOMS WILL NOT COMPLY
 WITH 32"CLEAR REQUIREMENT.
 5]1027[97SBC]SINGLE EXIT REQUIREMENT NOT
 IN COMPLIANCE TRAVEL DISTANCE[MAX.50']
 PROVIDE 2ND EXIT FROM EACH SPACE.
 6]HAVE STRUCTURAL ENGINEER SUBMIT DESIGN
 CRITERIA FOR THE MASONRY AND THEIR
 CONNECTIONS,SOUTH WALL IS MISSING
 COLUMNS,PROVIDE WALL SECTIONS FOR IN-
 TERIOR WALLS,SUBMIT FLOOR LOAD CALCUL-
 ATIONS FOR STORAGE OCCUPANCY SEE 1604
 [97SBC],SUBMIT ROOF DRAINAGE PLAN.
 7]PROVIDE COMPLETE STAIR DETAILS.
 8]GIVE DIMENSIONS ON ELEVATIONS INCLUDE
 PARAPETS AND DETAIL THEIR SUPPORTS.
 9]SUBMIT SPECIFICATIONS FOR
 ARCHITECTURAL TRIM,AND TEST REPORTS
 FOR EXTERIOR WINDOWS,DOORS AND ROOF
 COVER.
 10]COUNTY IMPACT AND CITY RADON FEES ARE
 DUE.