| Plan Review Notes For Permit 99110196 |
| Permit Number |
99110196 |
|
| Review Stop |
B |
| Sequence Number |
11 |
|
| Notes |
| Date |
Text |
| 2002-08-28 00:00:00 | | | | BUILDING PLAN REVIEW | | | PERMIT: 99110196 | | | ADD: 6107 S DIXIE HWY | | | CONT: DAAVID LANDY | | | TEL: (305)259-9900 | | | FL BLD CODE= 1997 STANDARD BUILDING CODE | | | | | | *****PROVISO***** | | | | | | 1) IDENTIY TENANT SEPERATION WALLS ABOVE | | | CEILING " FIRE SMOKE BARRIER PROTECT | | | ALL OPENINGS". | | | | | | 2)705.1.2 PENETRATIONS SHALL BE PRO- | | | TECTED BY AN APPROVED PENETRATION FIRE- | | | STOP SYSTEM AS TESTED IN ACCORDANCE WITH | | | ASTM E 814, WITH A MINIMUM POSITIVE | | | PRESSURE DIFFERENTIAL OF 0.01 INCH OF | | | WATER COLUMN AND AN F RATING OF NOT LESS | | | THAN REQUIRED RATING OF THE WALL | | | PENETRATED. PROVIDE MAN. SPEC AT TIME | | | OF INSPECTION. | | | | | | 3) 1203.4.2 EVERY TOLIET ROOM SHALL HAVE | | | WINDOWS AS SPECIFIED FOR HABITABLE ROOMS | | | PROVIDING IN NO CASE LESS THAN 3 SQ FT | | | OPEN SPACE OR HAVE APPROVED EQUIVALENT | | | VENTILATION. NOT SHOWN ON PLAN! | | | | | | 4) REVISION INDICATES FRONT WINDOWS | | | BLOCKED IN, FOR AT TIME OF C. O. | | | | | | 5) 1511.7 ARCHETECT TO INDICATE HOW ROOF | | | TOP MECHANICAL EQUIPMENT IS SECURED TO | | | THE ROOF DECK, EITHER 8" CURB OR RAISED | | | EQUIPMENT WITH A CLEAR HEIGHT OF 18". | | | SHOW ANCHOR DETAIL TO ROOF. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER |
|