 BUILDING PLAN REVIEW
 PERMIT: 99110196
 ADD: 6107 S DIXIE HWY
 CONT: DAAVID LANDY
 TEL: (305)259-9900
 FL BLD CODE= 1997 STANDARD BUILDING CODE
  
 *****PROVISO*****
  
 1) IDENTIY TENANT SEPERATION WALLS ABOVE
 CEILING " FIRE SMOKE BARRIER PROTECT
 ALL OPENINGS".
  
 2)705.1.2 PENETRATIONS SHALL BE PRO-
 TECTED BY AN APPROVED PENETRATION FIRE-
 STOP SYSTEM AS TESTED IN ACCORDANCE WITH
 ASTM E 814, WITH A MINIMUM POSITIVE
 PRESSURE DIFFERENTIAL OF 0.01 INCH OF
 WATER COLUMN AND AN F RATING OF NOT LESS
 THAN REQUIRED RATING OF THE WALL
 PENETRATED. PROVIDE MAN. SPEC AT TIME
 OF INSPECTION.
  
 3) 1203.4.2 EVERY TOLIET ROOM SHALL HAVE
 WINDOWS AS SPECIFIED FOR HABITABLE ROOMS
 PROVIDING IN NO CASE LESS THAN 3 SQ FT
 OPEN SPACE OR HAVE APPROVED EQUIVALENT
 VENTILATION. NOT SHOWN ON PLAN!
  
 4) REVISION INDICATES FRONT WINDOWS
 BLOCKED IN, FOR AT TIME OF C. O.
  
 5) 1511.7 ARCHETECT TO INDICATE HOW ROOF
 TOP MECHANICAL EQUIPMENT IS SECURED TO
 THE ROOF DECK, EITHER 8" CURB OR RAISED
 EQUIPMENT WITH A CLEAR HEIGHT OF 18".
 SHOW ANCHOR DETAIL TO ROOF.
  
 BUILDING PLAN REVIEW
 JIM WITMER