| 2002-08-23 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT:99110196 |
| | ADD: 6107 S DIXIE HWY |
| | CONT: DAVID LANDY |
| | TEL: (305)259-9900 |
| | 1997 STANDARD BUILDING CODE |
| | |
| | ****REVISION TO BUILDING SHELL PERMIT |
| | TO INCLUDE UNIT # 6 AS A BUILD OUT.***** |
| | |
| | 1) REVISION INDICATES THAT THE WINDOWS |
| | HAVE BEEN REMOVED ON THE FRONT OF THE |
| | BUILDING WHERE AS BUILDING IS BUILT WITH |
| | WINDOWS. |
| | |
| | 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 3)705.7.1 JOINTS INSTALLED IN OR BE- |
| | TWEEN FIRE RESISTANT WALLS, FIRE RESIS- |
| | TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES |
| | AND FIRE RESISTANT ROOFS OR ROOF/ CEIL- |
| | ING ASSEMBLIES SHALL BE PROTECTED BY AN |
| | APPROVED FIRE RESISTANT JOINT SYSTEM |
| | DESIGNED TO RESIST THE PASSAGE OF FIRE |
| | FOR A PERIOD NOT LESS THAN THE RE- |
| | QUIRED FIRE RESISTANCE RATING OF THE |
| | WALL, FLOOR OR FLOOR IN OR BETWEEN |
| | WHICH IT IS INSTALLED. |
| | |
| | 4) PROVIDE UL LISTING OF 1 HR TENANT |
| | SEPERATION WALL.704.1.3 |
| | |
| | 5) LISTED OCCUPANCY: BUSINESS NOT |
| | MERCANTILE, OTHERWISE COUNTY SHALL |
| | RE- ASSESS IMPACT FEES. |
| | |
| | 6) TABLE 803.3 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION; PROVIDE INFORMATION |
| | BASED ON INTERIOR FINISH REQUIREMENTS |
| | BASED ON OCCUPANCY |
| | |
| | 7)11-4.1.2 VERTICAL ACCESSIBILITY, |
| | NOTHING IN THIS CODE SHALL BE CONSTRUED |
| | TO RELIEVE THE OWNER OF ANY BUILDING, |
| | SSTRUCTURE OR FACILITY FROM THE DUTY TO |
| | PROVIDE VERTICAL ACCESSIBILITY TO ALL |
| | LEVELS ABOVE OR BELOW THE OCCUPIAABLE |
| | GRADE LEVEL. EXCEPTION FOR STORAGE 2ND |
| | FLOOR, CHAGE OF OCCUPANCY 2ND FLOOR WILL |
| | ENVOKE VERTICAL ACCESSIBILITY, INCLUDE |
| | NOTE OF EXCEPTION ON PLAN 2ND FLOOR! |
| | |
| | 8)11-4.1.3(3) GROUND & FLOOR SURFACES |
| | ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE |
| | ROOMS & SPACES SHALL COMPLY WITH |
| | 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE) |
| | A STATIC COEFFICIENT OF FRICTION OF 0.6 |
| | IS RECOMENDED FOR ACCESSIBLE ROUTES |
| | AND 0.8 FOR RAMPS. NO SCHEDULE? |
| | |
| | 9)1204.2 SURROUNDING MATERIALS; |
| | THE WALLS & FLOORS OF ALL PUBLIC REST- |
| | ROOMS SHALL BE LINED WITH NONABSORBANT |
| | MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE |
| | FLOOR. |
| | |
| | 10) 1203.4.2 EVERY TOLIET ROOM SHALL |
| | HAVE WINDOWS AS SPECIFIED FOR HABITABLE |
| | ROOMS PROVIDING IN NO CASE LESS THAN 3 |
| | SQ FT OPEN SPACE, OR HAVE APPROVED EQUIV |
| | ALENT VENTILATION. |
| | |
| | 11)1511.7 ROOF MOUNTED MECHANICAL UNIT |
| | S SHALL BE MOUNTED ON CURBS RAISED A |
| | MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| | FACE, OR WHERE ROOFING MATERIALS EXTEND |
| | BENEATH THE UNIT, ON RAISED EQUIPMENT |
| | SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| | HEIGTH OF 18". SHOW ANCHORAGE TO ROOF. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDEN- |
| | TIFYING THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND, WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | JIM WITMER |
| | PLAN REVIEW |
| | TEL: (561)659-8096 EX.8412 |
| | FAX: (561)659-8026 |