Plan Review Notes
Plan Review Notes For Permit 99110196
Permit Number 99110196
Review Stop B
Sequence Number 10
Notes
Date Text
2002-08-23 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT:99110196
 ADD: 6107 S DIXIE HWY
 CONT: DAVID LANDY
 TEL: (305)259-9900
 1997 STANDARD BUILDING CODE
  
 ****REVISION TO BUILDING SHELL PERMIT
 TO INCLUDE UNIT # 6 AS A BUILD OUT.*****
  
 1) REVISION INDICATES THAT THE WINDOWS
 HAVE BEEN REMOVED ON THE FRONT OF THE
 BUILDING WHERE AS BUILDING IS BUILT WITH
 WINDOWS.
  
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3)705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
  
 4) PROVIDE UL LISTING OF 1 HR TENANT
 SEPERATION WALL.704.1.3
  
 5) LISTED OCCUPANCY: BUSINESS NOT
 MERCANTILE, OTHERWISE COUNTY SHALL
 RE- ASSESS IMPACT FEES.
  
 6) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 7)11-4.1.2 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 SSTRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIAABLE
 GRADE LEVEL. EXCEPTION FOR STORAGE 2ND
 FLOOR, CHAGE OF OCCUPANCY 2ND FLOOR WILL
 ENVOKE VERTICAL ACCESSIBILITY, INCLUDE
 NOTE OF EXCEPTION ON PLAN 2ND FLOOR!
  
 8)11-4.1.3(3) GROUND & FLOOR SURFACES
 ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE
 ROOMS & SPACES SHALL COMPLY WITH
 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE)
 A STATIC COEFFICIENT OF FRICTION OF 0.6
 IS RECOMENDED FOR ACCESSIBLE ROUTES
 AND 0.8 FOR RAMPS. NO SCHEDULE?
  
 9)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 10) 1203.4.2 EVERY TOLIET ROOM SHALL
 HAVE WINDOWS AS SPECIFIED FOR HABITABLE
 ROOMS PROVIDING IN NO CASE LESS THAN 3
 SQ FT OPEN SPACE, OR HAVE APPROVED EQUIV
 ALENT VENTILATION.
  
 11)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGTH OF 18". SHOW ANCHORAGE TO ROOF.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026