Notes
Date Text
2001-01-08 00:00:00FAILED.NEED THE FOLLOWING INFORMATION
 SUPPLIED:
 NEED UNITY OF TITLE FOR PROPERTY TO THE
 NORTH (LOTS 1 & 2) WITH THIS PROPERTY.
 OWNER WANTS TO CROSS IT FOR WATER AND
 SANITARY HOOK-UPS.
 STORM WATER REQUIREMENTS:
 TO OBTAIN A CONSTRUCTION PERMIT THE
 FOLLOWING MUST BE SUBMITTED SIGNED AND
 SEALED BY A FLORIDA PROFESSIONAL
 ENGINEER (PE).
 1. CONSTRUCTION PLANS
 2. DETAILS AND SPECIFICATIONS
 3. HYDRAULIC COMPUTATIONS AND SUPPORTING
 DOCUMENTATION
 4.IMPERVIOUS AREA COMPUTATIONS
 5.POLLUTION PREVENTION PLAN.THE
 POLLUTION PREVENTION PLAN SHALL BE KEPT
 ON SITE AT ALL TIMES DURING
 CONSTRUCTION. THE PLAN SHALL BE
 INSTALLED IN THE FIELD PRIOR TO ANY
 EARTHWORK. THE ENGINEER OF RECORD SHALL
 CERTIFY TO THE CITY, ON A MONTHLY BASIS,
 THAT THE PLAN IS WORKING PROPERLY AND AS
 DESIGNED. THE ENGINEER OF RECORD IS
 RESPONSIBLE TO CERTIFY IMPLEMENTATION
 OF THE PROVISIONS OF CITY ORDINANCE NO.
 3132-98 OF THE CITY CODE AT SUCH TIME
 THE PERMITTEE APPLIES FOR A CERTIFICATE
 OF OCCUPANCY FROM THE CITY BUILDING
 OFFICIAL.
 6.EVERY SIX MONTHS AFTER CONSTRUCTION A
 PE SHALL CERTIFY THAT THE PERMANENT
 POLLUTION PREVENTION STRUCTURES, DRY-WET
 WATER DETENTION FACILITIES, AND
 EXFILTRATION SYSTEMS ARE WORKING AS
 DESIGNED AND ARE IN GOOD OPERATING
 CONDITION. ALL CERTIFICATIONS MUST BE
 SUBMITTED TO:
 STORM WATER UTILITY ENGINEER
 CITY OF WEST PALM BEACH PUBLIC UTILITIES
 DEPARTMENT
 P.O. BOX 3366, WEST PALM BEACH, FL 33402
 THE CERTIFICATION MUST INCLUDE THE
 BUILDING PERMIT NUMBER, THE ADDRESS OF
 THE PROPERTY AND THE NAME OF THE
 ESTABLISHMENT/PROJECT CONSTRUCTED.
 NO DUMPSTER SITE SHOWN.MUST MEET THE
 FOLLOWING;
 GARBAGE PICK-UP:
 STATE IF GARBAGE IS TO BE PICKED UP BY
 CITY OR IF IT IS PRIVATE PICKUP, IF TO
 BE PICKED UP BY THE CITY THEN THE
 FOLLOWING REQUIREMENTS MUST BE MET:
 1.DUMPSTER MUST HAVE A MINIMUM OF 12'-6"
 OPENING BETWEEN THE GATE POSTS.
 2.INTERIOR DIMENSIONS OF THE ENCLOSURE
 MUST BE A MINIMUM OF 12'-6" WIDE AND 12'
 DEEP.A CONCRETE PARKING STOP BARS 10'
 LONG MUST BE CENTERED (FROM GATES) AND
 INSTALLED 18" FROM THE BACK WALL.
 STEEL BARS WILL BE DRILLED THRU THE STOP
 BAR AND INTO THE INTERIOR FLOOR OF THE
 ENCLOSURE TO STOP THE BAR FROM MOVING
 WHEN THE DUMPSTER IS SET INSIDE.
 3.THE OPENING OF THE DUMPSTER ENCLOSURE
 MUST BE ANGLED SO THAT A 40' LONG TRUCK
 WITH THE FORKS EXTENDED CAN APPROACH THE
 OPENING AND PICK UP THE DUMPSTER WITHOUT
 TURNING A SHARP TURN.
 4.THE TRUCK NEEDS TO HAVE NO LESS THAN A
 16' HIGH VERTICAL CLEARANCE AREA FOR THE
 TRUCK TO PICK UP THE DUMPSTER. THE CLEAR
 AREA MUST OVER THE DUMPSTER AND WHERE
 THE TRUCK WILL BE STOPPED TO UNLOAD THE
 DUMPSTER.
 5.THE TRUCK NEEDS TO HAVE NO LESS THAN
 14' HIGH VERTICAL CLEARANCE AND 12'
 HORIZONTAL CLEARANCES FOR THE TRUCK TO
 DRIVE THROUGH.
 6.IT IS STRONGLY SUGGESTED THAT YOU ADD
 A RECYCLING CENTER TO YOUR DUMPSTER
 ENCLOSURE.
 7.SEE ATTACHED STANDARD DETAIL FOR
 FURTHER INFORMATION.