Plan Review Notes
Plan Review Notes For Permit 99110196
Permit Number 99110196
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************UNSAT********************
  
 1)NOTE:SUBMIT AIC RATING OF ALL
 EQUIPMENT MAINS/BRKRS ETC. AS PER 110-9
 215-5
  
 2)NOTE:AS PER 250-81 BLDG.STEEL IS ALSO
 TO BE INCLUDED AS PART OF THE GROUNDING
 ELECTRODE SYSTEM.
  
 3)NOTE:SHOW SECOND FLOOR ON PLANS AS
 EITHER EXISTING OR FUTURE.
  
 4)NOTE:PLANS DO NOT CORRELATE WITH
 EACHOTHER. THE ONE SMALL SET ATTACHED TO
 FRONT OF PLANS SHOW ALL MAIN DISCS BEING
 GROUPED FROM MAIN SERVICE. PLANS FROM
 E-1.0 SHOW SEPARATE METERS,DISCS ON THE
 BACK OF EACH UNIT???? WHICH ONE ?????
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF ANY QUESTIONS,,,,
 659-8096 EXT 8372