| Date |
Text |
| 2001-01-08 00:00:00 | LOCATION,TYPE AND AMOUNT OF FIXTURES ON |
| | THE SANITARY RISER DIAGRAMS DO NOT MATCH |
| | THE FLOOR PLAN.SUBMIT REVISED SANITARY |
| | RISER DIAGRAMS.COUNTYWIDE AMENDMENTS TO |
| | SPC SEC.104.2.1. |
| | |
| | THE BOTTOM OF THE WOOD BLOCKING BEHIND |
| | AND ON THE SIDE OF THE WATER CLOSET |
| | SHALL BE MAX.32" AFF.PER FAIR HOUSING |
| | ACT SEC.100.205 REQUIREMENT #6. |
| | |
| | ALL BATHROOMS WITHIN THE COVERED |
| | DWELLING UNIT SHALL COMPLY WITH THE |
| | PROVISIONS OF THE FEDERAL FAIR HOUSING |
| | ACT SECTION 3,24 CFR 100.205(C)(3)(IV) |
| | REQUIREMENT#7(2)PARAGRAPH (A)OR(B). |
| | CLEAR FLOOR SPACE SHALL BE PROVIDED AT |
| | FIXTURES TO ALLOW A PERSON IN A WHEEL- |
| | CHAIR OR OTHER MOBILITY AID USE OF THE |
| | FIXTURES.THE CLEAR FLOOR SPACE SHALL BE |
| | SHOWN ON THE PLANS AND DESIGNATE WHICH |
| | OPTION OF #7 (A OR B)IS BEING USED. |
| | |
| | CLEARLY SHOW WIDTH OF KIT.AREA BETWEEN |
| | CABINETS.COMPLY W/FEDERAL FAIR HOUSING |
| | ACT SEC.100.205 REQ.#7 (1)(C).SHOW 60" |
| | TURNING RADIUS ON PLANS. |
| | |
| | CLEAR FLOOR SPACE FOR RANGE SHALL BE |
| | CENTERED ON THE APPLIANCE PER FAIR |
| | HOUSING ACT REQ.#7 (1)(A).(SEE UNITS |
| | 1-L,2-L,1-R.SHOW THE CLEAR FLOOR SPACE |
| | ON THE PLANS. |