| Plan Review Notes For Permit 99101250 |
| Permit Number |
99101250 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************PROVISO******************* | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT BEING INSTALLED. AIC RATINGS | | | ARE FIGURED FROM FAULT CURRENT CALCU- | | | LATIONS. ABOVE PER ARTS:110-9/215-5 | | | 2)NOTE:AS PER ART:250-81 NEED TO SHOW | | | GROUNDING ELECTRODE CONDUCTOR GOING TO | | | GROUND ROD AND BUILDING STEEL ALSO. | | | 3)NOTE:PANEL SCHEDULE TO SHOW CIRCUT | | | REQ`D FOR BATH(S) CIRCUT AS PER ART: | | | 210-52D. | | | 4)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTER SPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | 5)NOTE:AS PER 1996 NFPA-72 CHAPTER ; | | | 2-2.1.1.1 SMOKE DETECTORS ARE REQ`D | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS | | | IN CONSTRUCTION OF NEW HOMES. | | | | | | NEED TO REVISE AND SUBMIT THE ABOVE | | | INFORMATION FOR REVIEW AND APPROVAL | | | BEFORE FIRST ROUGH ELECTRICAL INSPECTION | | | IS CALLED IN. |
|