| 2001-01-08 00:00:00 | PRODUCT APPROVAL FOR THE SLIDING WINDOWS |
| | IS EXPIRED.PROVIDE UPDATED REPORT. |
| | |
| | SLIDING WINDOWS ARE DESIGNED TO 75MPH & |
| | 20PSF PRESSURE. PROVIDE PRODUCT DESIGNED |
| | ACCORDING TO OUR WIND ZONE OF 110MPH AND |
| | 30PSF AS PER THE ENGINEER DESIGN COMPLIA |
| | NCE STATEMENT.1606 SBC 1997 |
| | |
| | THE ROOF PANELS ARE REQUIRED TO BE DESIG |
| | FOR A MINIMUM 20PSF LIVE LOAD.2002.2AMEN |
| | |
| | THE ROOF PANELS ARE REQUIRED TO HAVE |
| | TESTING AND COMPLY WITH CHAPTER 16 & 17 |
| | OF THE STANDARD BUILDING CODE.2002.2AMEN |
| | |
| | THE WALL AREA LOCATED ABOVE THE 6'COMMON |
| | WALL NEEDS TO BE OF 1 HOUR TYPE CONSTRUC |
| | TION & HAVE NO OPENINGS.TABLE 600 SBC |
| | |
| | THE ROOF AREA FOR 4' FROM THE COMMON |
| | WALL NEEDS TO BE OF FIRE RESISTANT CONST |
| | RUCTION. 704.4.1 SBC 1997 |
| | |
| | WINDOWS REQUIRED TO HAVE HURRICANE |
| | MISSLE IMPACT PROTECTION.1606.4 AMEND |
| | |
| | PLANS NEED PALM BEACH COUNTY IMPACT |
| | REVIEW. |
| | |
| | THE ROOF STRUCTURE CANNOT OVERHANG THE |
| | COMMON WALL. |
| | |
| | THIS SPACE WILL BE CONSIDERED LIVING |
| | SPACE AND WILL REQUIRE ELECTRIC TO CODE |
| | AND ENERGY CALCULATIONS. |
| | |
| | THE ENGINEER SHOP DRAWINGS PREPARED BY |
| | N KHANAL PE IS DESIGNED FOR A SCREENED |
| | STRUCTURE. PROVIDE A DRAWING ILLUSTRATIN |
| | A STRUCTURE CAPABLE OF PROVIDING WIND - |
| | RESISTANCE FOR A SOLID CLADDED ENCLOSURE |