| Plan Review Notes For Permit 99100989 |
| Permit Number |
99100989 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | NEED TO SUBMIT AIC RATING OF MAINS AND | | | EQUIPMENT. AS PER 110-9/215-5 | | | NEED TO SHOW GROUNDING ELECTRODE CONDUCT | | | GOING TO BLDG. STEEL ASLO. AS PER 250-81 | | | MISSING REC IN MASTER BATH GFI AS REQ`D | | | PER 210-52D AND ATLEAST ONE 20AMP CIRCUT | | | REQ`D TO BE LISTED ON PANEL SCHED. |
|