Plan Review Notes
Plan Review Notes For Permit 99100932
Permit Number 99100932
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************PROVISO******************
  
 1)NOTE:PAGE E-19 ALL PANELS AT DETACHED
 STRUCTURES,,G2,CW,G1,,,ARE TO HAVE
 GROUND RODS,FOOTER STEEL AND COLD WATER
 BOND (IF ANY).AS PER 250-24/250-81
 2)NOTE:SERVICE TO TC SHOWS EQUIPMENT
 GROUNDS BEING INSTALLED FROM METER/GUTT-
 -ER TO FIRST MEANS OF DISC!!!??
 EQUIPMENT GROUND IS ONLY TO BE INSTALLED
 AFTER FIRST MEANS OF DISC.
 3)NOTE:AS PER 215-5 ELECTRICAL RISER
 FOR G-2 AND PANEL FOR G-2 NEED TO MATCH
 FOR CONDUIT SIZE FEEDING PANEL CW!!
 4)NOTE:PAGE E-20 GATE HOUSE SERVICE....
 GROUNDING ELECTRODE CONDUCTOR IS TO GO
 TO COLD WATER BOND (IF ANY).
 5)NOTE,NOTE:ALL DISC.MEANS AT DETACHED
 STRUCTURES SHALL BE CLEARLY LABELED AS
 TO WHERE FEEDS ARE FROM!!!
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION IS CALLED IN