| Plan Review Notes For Permit 99100920 |
| Permit Number |
99100920 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***********PROVISO********************** | | | | | | 1)NOTE:PAGE E-19 ALL PANELS THAT ARE | | | FED FROM OTHER STRUCTURES NEED TO HAVE | | | SEPARATE GROND RODS,FOOTER STEEL AND | | | COLD WATER PIPE(IF ANY) AS PER ARTS: | | | 250-24A/250-81 | | | 2)NOTE:SERVICE FOR TRASH COMPACTOR SHOWS | | | EQUIPMENT GROUND BEING INSTALLED FROM | | | GUTTER/METER TO FIRST MEANS OF DISC. | | | EQUIPMENT GROUND IS ONLY TO BE INSTALLED | | | AFTER FIRST MEANS OF DISC. | | | 3)NOTE:PANEL G-1 REQ`S SEPARATE GROUND- | | | -ING.250-24A /250-81 | | | 4)NOTE:PANEL G-2 SHOWS 3/4 INCH CONDUIT, | | | PLEASE CHANGE TO 1"AS SHOWN ON RISER. | | | 5)NOTE:PAGE E-20 GROUNDING ELECTRODE | | | CONDUCTOR TO GO TO CWP(IFANY) | | | | | | NOTE:DETACHED STRUCTURES TO BE LABELED | | | AS TO WHERE FEEDS ARE FROM. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW AND | | | APPROVAL BEFORE FIRST ROUGH ELECTRICAL | | | INSPECTION IS CALLED IN. |
|