Plan Review Notes
Plan Review Notes For Permit 99100550
Permit Number 99100550
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************PROVISO*******************
  
 1)NOTE:PLEASE SUBMIT RISER DIAGRAM
 SHOWINGWIRE SISZES FROM METER TO PANEL
 AND FROM MIAN PANEL TO NEW 125 AMP
 PANEL BEING INSTALLED.
 2)NOTE:NEED TO SUBMIT PANEL SCHEDULES
 FOR BOTH PANELS.\\
 ALL THE ABOVE PER ART;215-5
  
 NEED TOSUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION IS CALLED
 IN.!!