| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************PROVISO******************* | | | | | | 1)NOTE:PLEASE SUBMIT RISER DIAGRAM | | | SHOWINGWIRE SISZES FROM METER TO PANEL | | | AND FROM MIAN PANEL TO NEW 125 AMP | | | PANEL BEING INSTALLED. | | | 2)NOTE:NEED TO SUBMIT PANEL SCHEDULES | | | FOR BOTH PANELS.\\ | | | ALL THE ABOVE PER ART;215-5 | | | | | | NEED TOSUBMIT THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL BEFORE FIRST | | | ROUGH ELECTRICAL INSPECTION IS CALLED | | | IN.!! |
|