| Plan Review Notes For Permit 99100534 |
| Permit Number |
99100534 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) LOAD CALCULATION NOT TO CODE60%???? | | | | | | 2) MAINS WILL HAVE TO BE GROUPED 230-72 | | | | | | 3) GROUND RODS TO BE TIED TOGETHER | | | 250-83 | | | | | | 4) SERVICE ENTRANCE CONDUCTORS AT | | | WEATHER HEAD ARE TO BE TIED INTO THE | | | SAME DROP FROM FPL!!230-2 | | | | | | 5) BRANCH CIRCUIT NUMBERS ARE TO BE ON | | | PLAN SHOWING WHICH OUTLET,LIGHT,AC | | | ARE ON THE CIRCUIT.110-22 |
|