| Permit Number |
99100504 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | THE AMOUNT OF REQUIRED PLUMBING FIXTURES | | | SHALL COMPLY W/SPC TABLE 407. | | | THE CALCULATIONS SUBMITTED BY REG ARCH. | | | FOR REQD.FIXTURES DON'T COMPLY W/SPC. | | | NO PROVISIONS ARE SHOWN FOR FUTURE | | | PLUMBING. | | | | | | SUBMIT HANDICAP DETAIL FOR DRINKING | | | FOUNTAIN.COMPLY W/FACBC SEC.4.15. | | | | | | CALCULATIONS FOR OVERFLOW DRAINAGE ARE | | | NOT CLEAR.SUBMIT CORRECT CALCULATIONS. | | | COMPLY W/SPC SEC.1109.1,1109.3,AND | | | APPENDIX "A" AND TABLE A101.2 OF SPC. | | | | | | SHT.P-2-SQ.FT.AREA ON ROOF DRAINS DOES | | | NOT MATCH SHT.P-4.CLARIFY. | | | | | | RELIEF LINE SHALL DISCHARGE TO EXTERIOR | | | PER COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 507.6. | | | | | | VENTS FOR TOILET ROOMS SHALL BE 3" PER | | | TABLE 920.2. | | | | | | SIZING OF HORIZONTAL SANITARY DRAINS | | | SHALL COMPLY W/SPC TABLE 714.1.(TOILET | | | ROOMS)AND 714.2. | | | APPROVED PLUMBER TO SUBMIT SEPERATE | | | PERMIT PRIOR TO STARTING ANY WORK. WRS |
|