Plan Review Notes
Plan Review Notes For Permit 99100503
Permit Number 99100503
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00JOB SPEC.15412-SEC.3.07-A TWO WAY
 CLEANOUT IS REQD.AT THE JUNCTION OF THE
 BUILDING DRAIN AND BUILDING SEWER PER
 SPC SEC.710.2.1.
  
 DRINKING FOUNTAINS SHALL COMPLY W/
 FACBC SEC.4.1.3(10)(A)-PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 SUBMIT DETAIL OF DRINKING FOUNTAIN.
 COMPLY W/FACBC SEC.4.15.
  
 SHT.A-20-SHOW ALL FIXTURE CLEARANCES
 OF HANDICAP FIXTURES.(CLEAR FLOOR SPACE
 UNDER LAVS.TO F.F.,HEIGHT OF H.C.URINAL
 AFF TO RIM,DISTANCE OF W.C.FROM FINISH
 WALL TO CENTERLINE OF BOWL,ETC.)
  
 SHT.A-21-SUBMIT UL LISTING FOR APPROVED
 FIRE SAFING DETAIL.COUNTYWIDE AMENDMENTS
 TO SPC SEC.104.2.4.
  
 CALCULATIONS FOR STORM DRAINAGE SYSTEM
 SHALL COMPLY W/ SPC SEC.1108.3 &
 APPENDIX "A",TABLE A101.2.
  
 PLUMBING FIXTURES SHALL BE WATER CON-
 SERVATION TYPE PER SPC SEC.406.NOTE SUCH
 ON SHT.P-1.
  
 SHT.P-1-FIXTURE SCHEDULE CALLS OUT
 COUNTERTOP LAVS.IN HANDICAP TOILET ROOMS
 COMPLY W/FACBC SEC.4.17.3(EXCEPTION:NEW
 CONSTRUCTION.)
  
 SHT.P-4-RAIN WATER LEADER TO 2ND.FLR.NOT
 SHOWN ON RISER.(SEE TOILET ROOMS.)
  
 INDICATE SLOPE OF OF STORM PIPING.COMPLY
 W/SPC TABLE 1108.1,108.2.
  
 FIXTURE MARKS ON FLOOR PLAN DON'T
 CORRELATE W/RISER DIAGRAM.CLARIFY.
 (P-9 NOT ON RISER,P-8 NOT ON SHT.P-2,P-3
 P-9 NOT ON SHT.P-2,P-3.,P-7 NOT SHOWN ON
 SHT.P-2.)
  
 DESIGN OF RISER ON P-4 DOESN'T MATCH
 P-2.CLARIFY.
  
 SIZE ALL SECTIONS OF THE SANITARY AND
 WATER RISERS.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.
  
  
  
  
 WATER SUPPLY SHALL COMPLY W/SPC 610.4.1,
 610.4.2.
  
 APPROVAL REQD.FROM CITY OF WPB ENGINEER-
 ING DEPT.FOR THE STORM DRAINAGE SYSTEM.
  
 SUBMIT MANUF.SHEETS FOR CHRONOMITE WTR.
 HEATER.SPC.501.2.503.2.
  
 CIRCUIT AND LOOP SYSTEM SHALL COMPLY W/
 SPC 914.1,914.3,920.3.