2001-01-08 00:00:00BREAK ROOM AND PANTRY SINK SHALL COMPLY
 W/FACBC SECS.4.24.1-4.24.7.(THESE AREAS
 ARE NOT CONSIDERED WORK AREAS.)SEE SHT.
 A-19,DETAILS #7 & #9.
  
 SUBMIT SIGNED AND SEALED PLANS PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.3
  
 SIZE OF HANDICAP STALLS (LXW) SHALL
 COMPLY W/FACBC SEC.4.17.3(SEE EXCEPTION:
 NEW CONSTRUCTION).
  
 WALLS IN TOILET ROOMS SHALL BE
 NONABSORBMENT TO A HEIGHT OF 4' PER SBC
 SEC.1204.2.
  
 SUBMIT RISER DIAGRAM FOR STORM DRAINAGE
 SYSTEM.SHOW SIZE OF ROOF DRAINS AND SQ.
 FOOTAGE DRAINED BY EACH DRAIN.SUBMIT
 CALCULATIONS FOR SECONDARY DRAINAGE PER
 SPC SEC.1109.1.INCLUDE PROVISIONS FOR
 THE PARAPET WALL PER SPC 1108.3.
  
 SUBMIT MOUNTING HEIGHT DETAILS AND
 DIMENSIONS FOR ALL HANDICAP FIXTURES AND
 APPURTENANCES.COMPLY W/FACBC OCT.1,1997
 EDITION.
  
 GRAB BARS SHALL COMPLY W/FACBC
 SEC.4.17.6
  
 DRINKING FOUNTAINS ARE REQD.PER SPC
 TABLE 407.
  
 DRAINAGE SYSTEM SHALL BE SIZED PER SPC
 TABLE 714.1,714.2.(MAX.OF 2 W.C.'S
 PERMITTED ON 3" BLDG.DRAIN.)
  
 SIZE ALL SECTIONS OF THE DWV SYSTEM AND
 WATER RISER PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.
  
 CIRCUIT AND LOOP SYSTEM SHALL COMPLY W/
 SPC 914.1,914.3.,920.3.
  
 SUBMIT MANUF.SHEETS FOR CHRONOMITE WTR.
 HEATER.SPC 501.2,503.2.