| Date |
Text |
| 2001-01-08 00:00:00 | BREAK ROOM AND PANTRY SINK SHALL COMPLY |
| | W/FACBC SECS.4.24.1-4.24.7.(THESE AREAS |
| | ARE NOT CONSIDERED WORK AREAS.)SEE SHT. |
| | A-19,DETAILS #7 & #9. |
| | |
| | SUBMIT SIGNED AND SEALED PLANS PER |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.3 |
| | |
| | SIZE OF HANDICAP STALLS (LXW) SHALL |
| | COMPLY W/FACBC SEC.4.17.3(SEE EXCEPTION: |
| | NEW CONSTRUCTION). |
| | |
| | WALLS IN TOILET ROOMS SHALL BE |
| | NONABSORBMENT TO A HEIGHT OF 4' PER SBC |
| | SEC.1204.2. |
| | |
| | SUBMIT RISER DIAGRAM FOR STORM DRAINAGE |
| | SYSTEM.SHOW SIZE OF ROOF DRAINS AND SQ. |
| | FOOTAGE DRAINED BY EACH DRAIN.SUBMIT |
| | CALCULATIONS FOR SECONDARY DRAINAGE PER |
| | SPC SEC.1109.1.INCLUDE PROVISIONS FOR |
| | THE PARAPET WALL PER SPC 1108.3. |
| | |
| | SUBMIT MOUNTING HEIGHT DETAILS AND |
| | DIMENSIONS FOR ALL HANDICAP FIXTURES AND |
| | APPURTENANCES.COMPLY W/FACBC OCT.1,1997 |
| | EDITION. |
| | |
| | GRAB BARS SHALL COMPLY W/FACBC |
| | SEC.4.17.6 |
| | |
| | DRINKING FOUNTAINS ARE REQD.PER SPC |
| | TABLE 407. |
| | |
| | DRAINAGE SYSTEM SHALL BE SIZED PER SPC |
| | TABLE 714.1,714.2.(MAX.OF 2 W.C.'S |
| | PERMITTED ON 3" BLDG.DRAIN.) |
| | |
| | SIZE ALL SECTIONS OF THE DWV SYSTEM AND |
| | WATER RISER PER COUNTYWIDE AMENDMENTS TO |
| | SPC SEC.104.2.1. |
| | |
| | CIRCUIT AND LOOP SYSTEM SHALL COMPLY W/ |
| | SPC 914.1,914.3.,920.3. |
| | |
| | SUBMIT MANUF.SHEETS FOR CHRONOMITE WTR. |
| | HEATER.SPC 501.2,503.2. |