| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****CORRECTED ON REVISION*************** | | | 1) PROVIDE OUTSIDE AIR CALCULATONS PER | | | ASHRAE 62-89 | | | 2) BATHROOM WINDOWS TO HAVE MIN. 3 SQ.FT | | | OPEN AREA OR BATHROOM EXHAUST FANS PER | | | 503.3.1 | | | 3) CEILING FANS BLADES TO BE MIN. 8' | | | FROM FINISHED FLOOR SMC 404.3.2 | | | 4) SHOW RETURN AIR PATH TO AHU #1 | | | 5) OVERFLOW PROTECTION REQUIRED FOR BOTH | | | UNITS SMC 304.8.6 | | | 6) DUCTS SHALL NOT BE INSTALLED WITHIN | | | 6" OF GROUND EXCEPT AS PROTECTED PER | | | SMC 607 1997 SMC 605.4 |
|