2001-01-08 00:00:00****CORRECTED ON REVISION***************
 1) PROVIDE OUTSIDE AIR CALCULATONS PER
 ASHRAE 62-89
 2) BATHROOM WINDOWS TO HAVE MIN. 3 SQ.FT
 OPEN AREA OR BATHROOM EXHAUST FANS PER
 503.3.1
 3) CEILING FANS BLADES TO BE MIN. 8'
 FROM FINISHED FLOOR SMC 404.3.2
 4) SHOW RETURN AIR PATH TO AHU #1
 5) OVERFLOW PROTECTION REQUIRED FOR BOTH
 UNITS SMC 304.8.6
 6) DUCTS SHALL NOT BE INSTALLED WITHIN
 6" OF GROUND EXCEPT AS PROTECTED PER
 SMC 607 1997 SMC 605.4