2001-01-08 00:00:00U*************UNSAT********************
  
 1)NOTE:AS PER ART;210-70 NEED TO SHOW
 EGRESS LIGHTING FROM SECOND FLOOR AND
 FROM FIRST FLOOR FRONT ROOM.MAYBE ON
 3-WAY FROM FRONT ENTRY.
 2)NOTE:AS PER ART;210-63 NEED WP GFI REC
 FOR A/C EQUIPMENT .
 3)NOTE:AS PER ARTS;215-5/110-9 NEED TO
 SHOW COMPLETE RISER DIAGRAM TO INCLUDE
 METER,MAINS,PANEL(S) GROUNDING SYSTEM,
 CONDUIT SIZES, WIRE SIZES ETC.
 NEED TO SUBMIT THE AIC RATING OF THE
 EQUIPMENT AND BREAKERS.AIC RATING IS
 FIGURED FROM FAULT CURRENT CALCULATIONS.
 NEED TO SUBMIT COMPLETE PANEL SCHEDULE
 AND LOAD CALCULATIONS.
 4)NOTE:AS PER ART 250-81 NEED TO INCLUDE
 GROUND ROD,COLD WATER PIPE AS A PART OF
 THE GROUNDING ELECTRODE SYSTEM.
  
  
 NEED TO SUBMIT THE ABOVE FOR REVIEW
 AND APPROVAL.
  
  
  
 APPROVED BY D. PALMER ON 11/3/99.