| Plan Review Notes For Permit 99100485 |
| Permit Number |
99100485 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | U*************UNSAT******************** | | | | | | 1)NOTE:AS PER ART;210-70 NEED TO SHOW | | | EGRESS LIGHTING FROM SECOND FLOOR AND | | | FROM FIRST FLOOR FRONT ROOM.MAYBE ON | | | 3-WAY FROM FRONT ENTRY. | | | 2)NOTE:AS PER ART;210-63 NEED WP GFI REC | | | FOR A/C EQUIPMENT . | | | 3)NOTE:AS PER ARTS;215-5/110-9 NEED TO | | | SHOW COMPLETE RISER DIAGRAM TO INCLUDE | | | METER,MAINS,PANEL(S) GROUNDING SYSTEM, | | | CONDUIT SIZES, WIRE SIZES ETC. | | | NEED TO SUBMIT THE AIC RATING OF THE | | | EQUIPMENT AND BREAKERS.AIC RATING IS | | | FIGURED FROM FAULT CURRENT CALCULATIONS. | | | NEED TO SUBMIT COMPLETE PANEL SCHEDULE | | | AND LOAD CALCULATIONS. | | | 4)NOTE:AS PER ART 250-81 NEED TO INCLUDE | | | GROUND ROD,COLD WATER PIPE AS A PART OF | | | THE GROUNDING ELECTRODE SYSTEM. | | | | | | | | | NEED TO SUBMIT THE ABOVE FOR REVIEW | | | AND APPROVAL. | | | | | | | | | | | | APPROVED BY D. PALMER ON 11/3/99. |
|