| Plan Review Notes For Permit 99100480 |
| Permit Number |
99100480 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***********PROVISO********************* | | | E-5 | | | 1)NOTE:NEED TO SUBMIT AIC RATING OF | | | MAINS,PANELS ETC.FIGURED FROM FAULT | | | CURRENT CALCULATIONS.REQ`D AS PER | | | 110-9/10 | | | 2)NOTE:NEED TO HAVE PLAGUES FOR SERVICE. | | | REQ`D AS PER 230-2B. | | | | | | E-1 | | | | | | NOTE:ACCESS TO WIREAND SUPPORT OF | | | FIXTURE AS PER 410-16 A/B |
|