| 2001-01-08 00:00:00 | FIXTURES DOWNSTREAM OF WATER CLOSET | | | SHALL BE VENTED PER SPC SEC.913.2. | | | | | | WATER CLOSETS NOT PERMITTED ON WET VENTS | | | PER COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 911.1.1. | | | | | | WASHING MACHINE SHALL NOT BE INSTALLED | | | ON 2" CROSS PER SPC SEC.409.12.3. | | | | | | LOCATION OF PLBG.FIXTURES ON SANITARY | | | RISER SHALL MATCH THE FLOOR PLAN PER | | | CITY OF WPB AMENDMENTS TO SPC. |
|