| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | WET VENTS SHALL RECEIVE THE DISCHARGE | | | FROM FIXTURE DRAINS ONLY PER CITY OF | | | WEST PALM BEACH AMENDMENTS TO THE STD. | | | PLUMBING CODE SEC.911.1.1. | | | | | | LOCATION OF FIXTURES ON PLUMBING RISER | | | SHALL MATCH THE FLOOR PLAN.CITY OF WPB | | | AMENDMENTS TO STD.PLBG.CODE SEC.104.2.1. | | | | | | MIN.SIZE OF OF DRAINAGE PIPE U/G SHALL | | | BE 2" PER SPC SEC.714.4. | | | | | | NUMBER OF WATER CLOSETS SHOWN ON PLBG. | | | RISER DOESN'T MATCH FLOOR PLAN.(4 NOTED | | | ON RISER,3 SHOWN ON FLOOR PLAN.) | | | | | | VENTS CANNOT BE LARGER THAN HORIZONTAL | | | DRAIN CONNECTED THERETO.SPC SEC.905.2. | | | (PERMITTED ONLY WHERE FROST IA A PROBLEM |
|