2001-01-08 00:00:00WET VENTS SHALL RECEIVE THE DISCHARGE
 FROM FIXTURE DRAINS ONLY PER CITY OF
 WEST PALM BEACH AMENDMENTS TO THE STD.
 PLUMBING CODE SEC.911.1.1.
  
 LOCATION OF FIXTURES ON PLUMBING RISER
 SHALL MATCH THE FLOOR PLAN.CITY OF WPB
 AMENDMENTS TO STD.PLBG.CODE SEC.104.2.1.
  
 MIN.SIZE OF OF DRAINAGE PIPE U/G SHALL
 BE 2" PER SPC SEC.714.4.
  
 NUMBER OF WATER CLOSETS SHOWN ON PLBG.
 RISER DOESN'T MATCH FLOOR PLAN.(4 NOTED
 ON RISER,3 SHOWN ON FLOOR PLAN.)
  
 VENTS CANNOT BE LARGER THAN HORIZONTAL
 DRAIN CONNECTED THERETO.SPC SEC.905.2.
 (PERMITTED ONLY WHERE FROST IA A PROBLEM