2001-01-08 00:00:00*************DENIED*********************
 ************SEE LIST********************
  
 1)NOTE:AS PER ARTS;215-5/110-9.NEED TO
 SHOW AIC RATING OF MAINS AND BRANCH
 BREAKERS.AIC RATING IS FIGUREDFROM FAULT
 CURRENT CALCULATIONS.
 2)NOTE:YOU SHOW MAIN DISC.BY CODE IF
 REQ`D.?? SOME FORM OF MAIN DISC.IS REQ`D
 EITHER MAIN BRKR. PANEL OR MAIN DISC.
 3)NOTE:AS PER ART:250-81 PLEASE SHOW
 GROUNDING ELECTRODE CONDUCTOR GOING TO
 BLDG.STEEL ALSO.
 4)NOTE:PLEASE LIST ON PANEL SCHEDULE
 CIRCUT(S) FOR BATH ROOM GFI AS PER ART;
 210-52D MUST BE 20 AMP.,#12 AWG.
 5)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTER SPACE ARE TO
 BE GFI/GFI PROTECTED.
 6)NOTE:PLEASE SHOW AIR HANDLER UNIT
 AND THE LOCATION BEING INSTALLED.
 IF AIR HANDLER IS GOING IN ATTIC ABOVE
 GARAGE THEN PLEASE DRAW IN RECEPT.REQ`D
 BY 210-63.
 7)NOTE:AS PER 1993/1996 NFPA-72 SMOKE
 DETECTORS ARE REQ`D AND SHALL BE
 INSTALLED INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS IN CONSTRUCTION OF NEW
 RESIDENTIAL DWELLINGS.
 8)NOTE:ALL LOW VOLTAGE MUST BE INCLUDED
 ON PLANS AT THE TIME OF SUBMITTAL.!!!
 IF LOW VOLTAGE IS NOT SUBMITTED AT THAT
 TIME, THEN A SEPARATE APPLICATION AND
 PLANS MUST BE SUBMITTED FOR REVIEWAND
 APPROVAL.
  
 NEED TO COMPLETE ALL THE ABOVE,SUBMIT
 FOR REVIEW AND APPROVAL. PLEASE CALL
 IF YOU HAVE ANY QUESTIONS.659-8096/8372