| Date |
Text |
| 2001-01-08 00:00:00 | *************DENIED********************* |
| | ************SEE LIST******************** |
| | |
| | 1)NOTE:AS PER ARTS;215-5/110-9.NEED TO |
| | SHOW AIC RATING OF MAINS AND BRANCH |
| | BREAKERS.AIC RATING IS FIGUREDFROM FAULT |
| | CURRENT CALCULATIONS. |
| | 2)NOTE:YOU SHOW MAIN DISC.BY CODE IF |
| | REQ`D.?? SOME FORM OF MAIN DISC.IS REQ`D |
| | EITHER MAIN BRKR. PANEL OR MAIN DISC. |
| | 3)NOTE:AS PER ART:250-81 PLEASE SHOW |
| | GROUNDING ELECTRODE CONDUCTOR GOING TO |
| | BLDG.STEEL ALSO. |
| | 4)NOTE:PLEASE LIST ON PANEL SCHEDULE |
| | CIRCUT(S) FOR BATH ROOM GFI AS PER ART; |
| | 210-52D MUST BE 20 AMP.,#12 AWG. |
| | 5)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS |
| | SERVING KITCHEN COUNTER SPACE ARE TO |
| | BE GFI/GFI PROTECTED. |
| | 6)NOTE:PLEASE SHOW AIR HANDLER UNIT |
| | AND THE LOCATION BEING INSTALLED. |
| | IF AIR HANDLER IS GOING IN ATTIC ABOVE |
| | GARAGE THEN PLEASE DRAW IN RECEPT.REQ`D |
| | BY 210-63. |
| | 7)NOTE:AS PER 1993/1996 NFPA-72 SMOKE |
| | DETECTORS ARE REQ`D AND SHALL BE |
| | INSTALLED INSIDE AND OUTSIDE ALL |
| | SLEEPING ROOMS IN CONSTRUCTION OF NEW |
| | RESIDENTIAL DWELLINGS. |
| | 8)NOTE:ALL LOW VOLTAGE MUST BE INCLUDED |
| | ON PLANS AT THE TIME OF SUBMITTAL.!!! |
| | IF LOW VOLTAGE IS NOT SUBMITTED AT THAT |
| | TIME, THEN A SEPARATE APPLICATION AND |
| | PLANS MUST BE SUBMITTED FOR REVIEWAND |
| | APPROVAL. |
| | |
| | NEED TO COMPLETE ALL THE ABOVE,SUBMIT |
| | FOR REVIEW AND APPROVAL. PLEASE CALL |
| | IF YOU HAVE ANY QUESTIONS.659-8096/8372 |