| Plan Review Notes For Permit 99100445 |
| Permit Number |
99100445 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)SHT.A-1-DRY VENTS ARE NOT PERMITTED | | | PER SPC SEC.906.2.1. | | | | | | 2)DESIGN OF CIRCUIT AND LOOP SYSTEM | | | SHALL COMPLY W/SPC SEC.914.1.VENTS SHALL | | | COMPLY W/SPC SEC.920.3.SIZE ALL VENTS. | | | | | | 3)SUBMIT A WATER RISER DIAGRAM FOR | | | REVIEW.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 104.2.1. | | | | | | 4)THE HANDICAP STALLS DO NOT COMPLY W/ | | | THE FACBC.SEE FACBC SEC.4.17.3(NEW | | | CONSTRUCTION.) | | | | | | 5)SUBMIT OCCUPANT LOAD FOR COMPLIANCE W/ | | | SPC TABLE 407 FOR MIN.NUMBER OF REQD. | | | FACILITIES.SEE 407.1.3. | | | | | | 6)FLOORS AND WALLS IN RESTROOMS SHALL BE | | | NONABSORBENT TO 4' PER SBC 1204.2(B). | | | | | | 7)FLOOR DRAINS ARE READ.IN THE RESTROOMS | | | PER SPC SEC.409.4.1.1 | | | | | | 8)DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | | SEC.4.1.3.(10)(A).PROVISIONS SHALL BE | | | MADE FOR PEOPLE WHO HAVE TROUBLE BENDING | | | OR STOOPING. | | | | | | 9)SINK SHALL COMPLY W/FACBC SECS.4.24.1- | | | 4.24.7. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. |
|