| Plan Review Notes For Permit 99100387 |
| Permit Number |
99100387 |
|
| Review Stop |
P |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)HORIZONTAL DRY VENTS NOT PERMITTED PER | | | SPC SEC.906.2.1.(SEE FLOOR SINKS,FLOOR | | | DRAINS.) | | | | | | 2)GREASE INTERCEPTOR SHALL COMPLY W/CITY | | | OF WPB ENGINEERING STANDARDS. | | | | | | 3)WATER SUPPLY CONTROL SHALL COMPLY W/ | | | SPC SEC.610.4.1,610.4.2. | | | | | | 4)SERIES OF FLOOR DRAINS AND FLOOR SINKS | | | SHALL COMPLY W/SPC SEC.921 FOR HORIZ. | | | COMBINATION WASTE AND VENT SYSTEM. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|