| Plan Review Notes For Permit 99100387 |
| Permit Number |
99100387 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SIZE AND DESIGN OF GREASE TRAP SHALL BE | | | APPROVED BY CITY OF WPB UTILITIES.SUBMIT | | | APPROVAL FORM FROM UTILITIES.CONTACT | | | R.COMPO AT (561)835-7423 FOR INFO. | | | | | | PLANS SHALL BE ROUTED TO FLA.DEPT.OF | | | BUSINESS REGULATION FOR REVIEW AND | | | APPROVAL PRIOR TO REVIEW BY THIS DEPT. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.101.4.7 | | | | | | URINAL SHALL BE ARRANGED TO ALLOW FOR | | | PRIVACY PER SPC SEC.404.3.(URINAL IS | | | LOCATED IN LINE OF SIGHT FROM CORRIDOR) | | | | | | HUB DRAINS NOT PERMITTED PER SPC.FLOOR | | | DRAINS OR FLOOR SINKS SHALL BE INSTALLED | | | PER SPC 407 & 408. | | | | | | VENTING OF FLOOR DRAINS AND FLOOR SINKS | | | SHALL COMPLY W/TABLE 908.1. | | | | | | WATER SUPPLY CONTROL FOR THE RESTROOMS | | | SHALL COMPLY W/SPC SEC.610.4.1. | | | | | | DRY VENTS NOT PERMITTED PER SPC 906.4 | | | | | | SHOW HEIGHT OF TOILET PAPER DISPENSER | | | PER FACBC FIG.30. | | | | | | SHOW VTR FOR TOILET ROOM OR CONNECTION | | | TO STACK VENT.SPC SEC.904.2.1. |
|