| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE:AS ASKED FOR ON FIRST SET OF NOTE | | | -S. PLEASE SUBMIT LOAD CALCULATIONS. | | | PLEASE SHOW,,,WITH SQFT/CONTINUOUS LOADS | | | AT 125% ETC. | | | | | | 2)NOTE: PLEASE SUBMIT AND SHOW ALL AIC | | | RATING FOR ALL MAINS/PANELS BEING INSTAL | | | -LED.EQUIPMENT MUST BE RATED FOR THE | | | AVAILABLE FAULT CURRENT PER 110-9 | | | | | | \\3)NOTE PLEAS SUBMIT AND SHOW GROUNDING | | | ELECTRODE SYSTEM. 250-50 BLDG STEEL AND | | | COLD WATER ETC. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMAITON | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|