2001-01-08 00:00:00INDICATE SIZE OF GREASE TRAP ON PLANS.
 CONTACT RODNEY COMPO AT CITY OF W.P.B.
 REGIONAL WASTEWATER TREATMENT PLANT AT
 (561)835-7423 FOR SIZE REQS.
  
 PLANS SHALL BE ROUTED TO DEPT.OF
 BUSINESS AND PROFESSIONAL REGULATION FOR
 REVIEW AND APPROVAL PRIOR TO REVIEW BY
 THIS AGENCY.SPC SEC.101.4.7.
  
 URINAL SHALL BE ARRANGED TO ALLOW FOR
 PRIVACY PER SPC SEC.404.3.(LOCATED IN
 LINE OF SIGHT IN CORRIDOR.)
  
 HUB DRAINS NOT PERMITTED BY SPC.FLOOR
 DRAINS OR FLOOR SINKS SHALL BE INSTALLED
 PER SPC 407 AND SPC 807.
  
 LOCATION OF GREASE TRAP SHALL COMPLY W/
 SBC SEC.1803.1.3.
  
 FLOOR DRAINS ARE NOT PROPERLY VENTED PER
 SPC 901.2 AND TABLE 908.1.
  
 VENTS CANNOT BE INCREASED IN SIZE .(ONLY
 IN AREAS WHERE FROST IS A FACTOR.)SPC
 SEC.905.2.
  
 WATER CLOSETS ARE NOT PROPERLY VENTED
 PER SPC SEC.901.2
  
 SIZE THE WATER SUPPLY SYSTEM IN ITS
 ENTIRETY.SPC SEC.104.2.1.
  
 WATER SUPPPLY CONTROL FOR THE RESTROOMS
 SHALL COMPLY W/SPC SEC.610.4.2.
  
 SUBMIT GAS DRAWING IF APPLICABLE.SPC
 104.2.1.
  
 DRY VENTS ARE NOT PERMITTED ON W.C.'S
 PER SPC SEC.906.4.
  
 SHOW HT. OF TOILET PAPER DISPENSER
 ON PLANS .COMPLY W/FACBC FIG 30.