| Date |
Text |
| 2001-01-08 00:00:00 | INDICATE SIZE OF GREASE TRAP ON PLANS. |
| | CONTACT RODNEY COMPO AT CITY OF W.P.B. |
| | REGIONAL WASTEWATER TREATMENT PLANT AT |
| | (561)835-7423 FOR SIZE REQS. |
| | |
| | PLANS SHALL BE ROUTED TO DEPT.OF |
| | BUSINESS AND PROFESSIONAL REGULATION FOR |
| | REVIEW AND APPROVAL PRIOR TO REVIEW BY |
| | THIS AGENCY.SPC SEC.101.4.7. |
| | |
| | URINAL SHALL BE ARRANGED TO ALLOW FOR |
| | PRIVACY PER SPC SEC.404.3.(LOCATED IN |
| | LINE OF SIGHT IN CORRIDOR.) |
| | |
| | HUB DRAINS NOT PERMITTED BY SPC.FLOOR |
| | DRAINS OR FLOOR SINKS SHALL BE INSTALLED |
| | PER SPC 407 AND SPC 807. |
| | |
| | LOCATION OF GREASE TRAP SHALL COMPLY W/ |
| | SBC SEC.1803.1.3. |
| | |
| | FLOOR DRAINS ARE NOT PROPERLY VENTED PER |
| | SPC 901.2 AND TABLE 908.1. |
| | |
| | VENTS CANNOT BE INCREASED IN SIZE .(ONLY |
| | IN AREAS WHERE FROST IS A FACTOR.)SPC |
| | SEC.905.2. |
| | |
| | WATER CLOSETS ARE NOT PROPERLY VENTED |
| | PER SPC SEC.901.2 |
| | |
| | SIZE THE WATER SUPPLY SYSTEM IN ITS |
| | ENTIRETY.SPC SEC.104.2.1. |
| | |
| | WATER SUPPPLY CONTROL FOR THE RESTROOMS |
| | SHALL COMPLY W/SPC SEC.610.4.2. |
| | |
| | SUBMIT GAS DRAWING IF APPLICABLE.SPC |
| | 104.2.1. |
| | |
| | DRY VENTS ARE NOT PERMITTED ON W.C.'S |
| | PER SPC SEC.906.4. |
| | |
| | SHOW HT. OF TOILET PAPER DISPENSER |
| | ON PLANS .COMPLY W/FACBC FIG 30. |