| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO: | | | ADDITIONAL MECHANICAL PERMITS REQUIRED | | | FOR HOODS, SUPPRESSION SYSTEMS, AND WALK | | | IN COOLER/ FREEZER. SUBMIT PLANS WITH | | | MECHANICAL PERMIT APPLICATIONS | | | CLEARANCE TO COMBUSTIBLES FOR HOOD AND | | | DUCT TO BE 18" MIN. OR CLEARANCE REDUCT- | | | ION IN ACCORDANCE WITH 1997 SMC 504.4 | | | AND 505.12 | | | EXHAUST TERMINATION TO BE MIN. 10' FROM | | | ANY OUTSIDE AIR INTAKE |
|